2004-11-18 00:00:00DENIED: BUILDING 3 UNIT 17
 MONACO - END UNIT:
  
 COMMENT FROM REVIEW DATED 7-20-04 WAS
 NOT ADDRESSED.RETURN AIR JUMPER FROM
 THE MASTER BEDROOM IS NOT SIZED
 PROPERLY.ALL SUPPLY AIR INTO THE
 MASTER SUITE IS TO BE INCLUDED FOR A
 TOTAL OF SUPPY AIR INTO THAT AREA.R/A
 JUMPER SHALL BE A MINIMUM OF 1 1/2
 TIMES
 THAT OF THE SUPPLY AIR INTO THE MASTER
 SUITE.
  
 PLEASE NOTE FAN SCHEDULE INDICATES EF-3
 GARAGE FAN.THIS IS NOT INDICATED ON
 THE PLAN.PLEASE CLARIFY.
  