2004-07-20 00:00:00DENIED:"MONACO MODEL" END-UNIT
 1.RETURN AIR FROM THE MASTER BEDROOM
 IS NOT SIZED PROPERLY.PER THE REVISED
 2001 FBC(M) 601.4 EXCEPTION #1; TRANSFER
 DUCTS SHALL BE A MINIMUM OF 1 1/2 TIMES
 THE SQUARE INCHES OF THE SUPPLY AIR TO
 THAT SPACE.EXCEPTION #3; ALL AIR INTO
 THE MASTER SUITE SHALL BE INCLUDED.SEE
 THE ATTACHED SCHEDULE FOR PROPER SIZING
 OF THE RETURN AIR JUMPER.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2, 402.2.1 OR 403.3.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PLANS ARE TO BE SIGNED AND DATED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES AND THE FLORIDA
 ADMINISTRATIVE CODE.
  