Date |
Text |
2004-06-24 00:00:00 | **************** UNSAT ************** |
| BLDG #3 |
| |
| 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| AND CORRELATE WITH SUBMITTED PANEL |
| SCHEDULE. |
| |
| 2)NOTE: PLEASE SEE MISPRINT ON PLANS |
| FOR ARC FAULT PROTECTION 210.12 |
| |
| 3)NOTE: PLEASE SEE OCP FOR AHU IS MUCH |
| LARGER THAN OCP FO CU, YET LOAD CALCS |
| INDICATE CU LOAD.? |
| PLEASE CORRLEATE W/ MECH PLANS. |
| |
| 4)NOTE: PLEASE SEE NFPA-72 8-1.4.2, |
| SD LOCATIONS. 3'FROM BATHS/KITCHENS, |
| 5' FROM RA'GRILLES, 3'FROM SUPPLY, |
| 20' FROM COOKING APPLIANCE, W/ EXCEPT. |
| |
| 5)NOTE: PLEASE SHOW A/C CU DISCONNECTS |
| PER 440.11 |
| |
| 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| FS 471.023. |
| PLEASE INCLUDE ALL RQUIRED LICENSE #'S |
| ON TITLE BLOCK. |
| PLEASE SEE ATTACHED PRINT OUT FROM STATE |
| DBPR'S SITE. FIRM SHOWN ON TITLE BLOCK |
| HAS A "CLOSED" LICENSE? |
| PLEASE SEE THE ABOVE IS REQUIRED FOR ALL |
| TRADES AND SHEETS WHEATHER OR NOT |
| COMMENTS ARE MADE BY OTHER REVIEWERS. |
| |
| PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |