2004-11-19 00:00:00 | PROVISO:BUILDING 5 UNIT 24 | | GENEVA END UNIT | | THE EXHAUST FAN SCHEDULE INDICATED ON | | PLAN SHEET M-4 SHOWS EF-2 & EF-3 FOR THE | | KITCHEN AND GARAGE EXHAUST WHICH ARE NOT | | INDICATED ON THE PLAN.PLEASE CLARIFY, | | | | PLEASE NOTE PLAN M-2 MONACO END UNIT IS | | NOT APPROVED.THE R/A FROM THE MASTER | | SUITE IS NOT SIZED IN ACCORDANCE WITH | | 2001 FBC(M) 601.4 EXCEPTION #1 & 3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS @ (561)805-6719. | | |
|