Date |
Text |
2004-07-19 00:00:00 | ****CORRECTIONS**** |
| |
| BLDG 1 - 04060859, 04060870, 04060872, |
| 04060874, 04060875, 04060878 |
| |
| BLDG 2 - 04060879, 04060881, 04060883, |
| 04060884, 04060886 |
| |
| BLDG 3 - 04060897, 04060896, 04060895, |
| 04060894, 04060893, 04060892 |
| |
| BLDG 4 - 04060754, 04060721 |
| |
| BLDG 5 - 04060887, 04060888, 04060889, |
| 04060890, 04060891 |
| |
| BLDG 6 - 04060861, 04060863, 04060865, |
| 04060866 |
| |
| BLDG 7 - 04060867, 04060868 |
| |
| BLDG 8 - 04060856, 04060855 |
| |
| BLDG 9 - 04060842, 04060786 |
| |
| BLDG 10- 04060869, 04060871, 04060873 |
| |
| BLDG 11- 04060880, 04060882 |
| |
| BLDG 12 - 04060876, 04060877 |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)SEPARATE PERMITS REQUIRED FOR |
| TRADES. |
| |
| 3.)DECLARE A CONSTRUCTION TYPE. SHEET |
| A1, CODE COMPLIANCE, REFERS TO BOTH |
| TYPE IV UNPROTECTED AND TYPE IV 1 HR. |
| THE PLANS MUST COMPLY WITH THE |
| CONSTRUCTION TYPE DECLARED. |
| |
| 4.)PROVIDE AREA CALCS FOR THE UNITS |
| INCLUDING CONDITIONED AND UNCONDITIONED |
| SPACE. |
| |
| 5.)PROVIDE THE PRINTED NAME OF THE |
| PERSON WHO PREPARED THE ENERGY CALCS. |
| SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| CALCS. |
| |
| 6.)THE JURISDICTION NUMBER FOR THE |
| ENERGY CALCS IS 604700.FOR EACH |
| UNIT TYPE, INCLUDE THE PERMIT NUMBERS. |
| |
| 7.)FLORIDA STATE, LOCAL OR SITE |
| SPECIFIC PRODUCT APPROVALS REQUIRED |
| IN ADDITION TO THE TEST REPORTS.FAC9B72. |
| WWW.FLORIDABUILDING.ORG |
| PRODUCT APPROVALS NOT SUBMITTED PROPERLY |
| BEFORE ISSUANCE WILL REQUIRE SEPARATE |
| PERMITS FOR THOSE ITEMS. |
| |
| 8.)FOR UNITS WHICH HAVE A NEGATIVE |
| DESIGN PRESSURE OF -126.4 (S3.2), THIS |
| EXCEEDS THE PRODUCT LIMITATION (SEE |
| PRODUCT APPROVAL, WINDOW). |
| |
| 9.) THE KD WINDOW PRODUCT APPROVALS ARE |
| ILLEGIBLE.PROVIDE LEGIBLE COPIES |
| SO THAT THEY CAN BE REVIEWED FOR CODE |
| COMPLIANCE.PROVIDE WINDOW MULLION |
| PRODUCT APPROVALS. |
| |
| 10.) INDICATE WHICH ANCHORS ARE BEING |
| USED FOR THE HURRICANE SHUTTERS; |
| COMPLETE AN INSTALLATION SCHEDULE (SEE |
| ATTACHED). |
| |
| 11.) PROVIDE PRODUCT APPROVALS AND |
| TEST REPORTS FOR THE SHINGLES AND FLAT |
| TILE.MAY BE SUBMITTED WITH ROOF |
| PERMIT APPLICATION.PLEASE NOTE ANY |
| HEIGHT LIMITATION WHICH MAY BE ON THE |
| SHINGLE PRODUCT APPROVAL. |
| |
| 12.) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY BEFORE A PERMIT CAN BE |
| ISSUED.THE PLANS MUST BE STAMPED AND |
| THE RECEIPT ATTACHED TO THE APPLICATION. |
| 233-5025 |
| |
| 13.)PROVIDE A SOILS INVESTIGATION |
| REPORT. |
| |
| 14.)PROVIDE A SURVEY FOR THIS |
| PROPERTY. |
| |
| 15.)FOR ARCHITECTS, SEE FAC61G1-16. |
| 003, 004.THE PRINTED NAME OF THE |
| PERSON SEALING THE PLAN IS TO BE ON |
| EACH SHEET.THE SEAL IS TO BE LEGIBLE. |
| |
| 16.)SHEET S1.2, ROOF FRAMING PLAN, |
| SHOWS THE TRUSSES AS WOOD WHICH IS NOT |
| CONSISTENT WITH OTHER NOTES AND DETAILS |
| ON THE PLAN. |
| |
| 17.)SHOW HOW THE STRUCTURAL INTEGRITY |
| AND FIRE RESISTANCE OF THE 2 HR TENANT |
| SEPARATION WALL WILL BE MAINTAINED WITH |
| THE PENETRATION OF THE FLOOR SYSTEM. |
| SHOW HOW THE WALL WILL MAINTAIN ITS |
| STRUCTURAL INTEGRITY INDEPENDENT OF THE |
| UNIT ON THE OPPOSITE SIDE OF THE WALL. |
| FBC704.4.2.; SECTION 2-A5.INCLUDE |
| THE SHEATHING WHEN SHOWING THE |
| INDEPENDENCE OF THE STRUCTURAL |
| INTEGRITY. |
| |
| 18.)PROVIDE CALCULATIONS TO SHOW THAT |
| SOFFIT VENTS COMPLY WITH FBC2309.7. |
| |
| 19.)PROVIDE ATTIC ACCESS LOCATION. |
| |
| 20.)TWO WALL SECTIONS HAVE BEEN |
| PROVIDED (END UNIT EXTERIOR, SECTION |
| BETWEEN UNITS 22 & 23).PLEASE PROVIDE |
| A TYPICAL DETAIL FOR THE CONDITION |
| WHICH OCCURS BETWEEN 20/21, 21/22, 23/24 |
| DUE TO ELEVATION CHANGES.ALSO SHOW |
| FOR OTHER BUILDINGS WHERE THIS |
| CONDITION APPLIES. |
| |
| 21.)A 1X2 FIRESTOP IS SHOWN ON SECTION |
| B-A4.THIS IS REQUIRED AT ALL FLOORS |
| FBC705.3. |
| |
| 22.)SECTION 3-A5, THE TENANT |
| SEPARATION OPTION, HOW WILL THIS WALL |
| SUPPORT THE STEEL TRUSSES?PLEASE ALSO |
| REWORD THE SECTION; CURRENTLY STATES |
| "OPTIONAL" BUT THE SEPARATION IS |
| MANDATORY.I BELIEVE THIS SHOULD BE |
| "OPTION". |
| |
| 23.)SECTION 3-A5, PROVIDE MORE DETAIL |
| SPECIFIC TO UL DESIGN U411.FOR |
| INSTANCE, THE GYPSUM BOARD IS SHOWN |
| DOUBLE GRAPHICALLY BUT SHOULD BE IN |
| PRINT AS WELL, ALONG WITH THE ATTACHMENT |
| REQUIRED BY UL411. |
| |
| 24.)ROOF/CEILING ASSEMBLIES ARE TO BE |
| OF NONCOMBUSTIBLE CONSTRUCTION IN TYPE |
| IV PER FBC TABLE 600.NOTE E STATES |
| THAT FIRE RETARDANT TREATED WOOD IS TO |
| BE USED IN BUILDINGS NOT OVER TWO |
| STORIES.PLEASE ADDRESS. |
| |
| 25.)SECTION 1-A5 SHOWS FIRE RESISTANT |
| PLYWOOD ON THE ENTIRE ROOF; 2-A5 APPEARS |
| TO SHOW IT FOR 4' ONLY. |
| |
| 26.)SPECIFY INSULATION ON THE |
| WALL SECTIONS. |
| |
| 27.)PROVIDE A BALCONY GUARDRAIL |
| DETAIL; COMPLY WITH 1608.2.2 AND 1015. |
| |
| 28.)YOU CANNOT GIVE CODE REFERENCES |
| AS A SPECIFICATION (SUCH AS SECTION2-A6) |
| FBC104.2.1.PROVIDE DETAILS AND VERBAGE |
| IN COMPLIANCE WITH THE CODE SECTIONS. |
| SHOW ATTACHMENT FOR THE HANDRAIL |
| TO COMPLY WITH 1608.2.1. |
| |
| 29.) 4-S2.3 SHOWS A GIRDER TRUSS WITH |
| PLYWOOD; TYPE IV DOES NOT ALLOW |
| COMBUSTIBLE/UNPROTECTED.OTHER DETAILS |
| ALSO SHOW WOOD, WOOD CONNECTORS. |
| IT APPEARS THAT THE STRUCTURALS SHOW |
| WOOD, ARCHITECTURALS SHOW METAL TRUSSES. |
| DETERMINE THE BUILDING TYPE AND |
| MAKE ALL DETAILS CODE COMPLIANT. |
| |
| 30.)THE CONNECTOR HUS210-2 IS A |
| WOOD TO WOOD USED IN A WOOD TO MASONRY |
| OR CONCRETE APPLICATION (ROOF FRAMING |
| HOLD DOWN ANCHOR SCHEDULE, S1.2). |
| PROVIDE ALLOWABLE UPLIFT FOR HETA20. |
| FASTENING OF PA28 CONFLICTS WITH |
| CATALOG.ADDRESS. |
| |
| 31.)PROVIDE INFORMATION TO SHOW HOW |
| THE HOLLOW CORE PLANK WILL HANDLE |
| THE LINE LOAD OF THE CMU WALLS. |
| |
| 32.) WINDOW BUCK TO GIVE FULL SUPPORT |
| OF THE WINDOW, FBC1707.4.4.2 (A7). |
| |
| 33.) S.01, PRE-ENGINEERED WOOD TRUSSES |
| GIVE REFERENCE TO DESIGN CRITERIA FOR |
| THE TRUSSES IN THE CONTRACT DOCUMENTS. |
| PLEASE PROVIDE ON THE PLAN. |
| |
| 34.) S1.2, ROOF UPLIFT SCHEDULE, ZONE |
| 3 IS TO COMPLY WITH CITY OF WEST PALM |
| BEACH AMENDMENTS TO THE FBC, CHAPTER |
| 23 REVISED 2306.1. |
| |
| 35.) WHEN RESUBMITTING, REPLACE ONLY |
| SHEETS WHICH HAVE CHANGED.SUBMIT OLD |
| SHEETS SEPARATELY.INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED. |
| |
| 36.) GENERAL COMMENT; ON SOME OF THE |
| PLANS SOME SHEETS WERE UNSEALED |
| PHOTOCOPIES.FAC61G15-23.002 REQUIRES |
| THAT ALL SETS ARE ORIGNAL SIGNED, |
| SEALED AND DATED PLANS.DO NOT SUBMIT |
| PHOTOCOPIES OF SEALED DOCUMENTS. |
| |
| 37.) THE GARAGE JAMB DETAIL C-A6 |
| CONFLICTS WITH THE ATTACHMENT ON THE |
| PRODUCT APPROVAL SUBMITTED. |
| |
| 38.) PROVIDE FIRE SPRINKLER PLANS; |
| FBC104.3.1.1, MINIMUM PLAN REVIEW |
| CRITERIA, RESIDENTIAL, ITEM #3. |
| |
| 39.) ON THE SITE PLAN, CLEARLY INDICATE |
| THE DISTANCE FROM EACH BUILDING TO THE |
| PROPERTY LINE, AS WELL AS THE PROPERTY |
| LINE TO THE CENTER OF THE ROAD FOR |
| REVIEW FOR TABLE 600 COMPLIANCE.THIS |
| APPEARS FOR SOME BUILDINGS (FOR EXAMPLE, |
| BUILDING #2) BUT NOT OTHERS.ALSO NOTE |
| THE DISTANCE BETWEEN 6 AND 7.IT IS |
| UNCLEAR AS TO THE DISTANCE TO THE |
| PROPERTY LINE AND TO CENTERLINE OF THE |
| STREET ON THE REAR OF BUILDING 11. |
| BUILDING 10 DIMENSIONS ARE NOT LEGIBLE. |
| PROVIDE THE DISTANCE BETWEEN BUILDING |
| 12 AND THE CABANA.IF NECESSARY TO |
| SHOW TABLE 600 COMPLIANCE, PROVIDE |
| AN ELEVATION OF THE CABANA (WEST SIDE). |
| |
| 40.) INDICATE RISE AND RUN FOR THE |
| ENTRY STAIRS. |
| |
| 41.) ADDITIONAL FEES WILL BE DUE (VALUE |
| ADJUSTMENT) AFTER CORRECT CONDITIONED |
| AND UNCONDITIONED SQUARE FOOTAGE IS |
| DETERMINED. |
| |
| 42.) PROVIDE A FIREBLOCKING DETAIL FOR |
| THE DROPPED SOFFIT FBC705.3.1.1 AND |
| THE STAIR FBC2305.1.5 (A6). |
| |
| 43.) SHEET S01, WOOD TRUSSES NOTE 2 |
| REFERS TO TPI-85.THE CORRECT |
| REFERENCE IS TPI 95, FBC2319.17.2. |
| |
| 44.) PROVIDE THE MEAN ROOF HEIGHT. |
| BEFORE RESUBMITTAL CONFIRM THAT THE |
| MEAN ROOF HEIGHT DOES NOT EXCEED THE |
| PRODUCT LIMITATION, IF ANY, OF THE |
| ROOF SHINGLE PRODUCT APPROVAL. |
| |
| 45.)DUE TO THE SCOPE AND NATURE OF |
| THE CONSTRUCTION, A RESIDENT INSPECTOR |
| WILL BE REQUIRED.PLEASE CONTACT |
| HAROLD PISKURA, 561-805-6711. |
| |
| 46.)MASTER BATH WINDOWS ARE TO COMPLY |
| WITH FBC2405.2.1(2) IF THEY ARE WITHIN |
| 36".PLEASE NOTE ON FLOOR PLAN. |
| |
| THE FOLLOWING COMMENTS APPLY TO |
| BUILDINGS 7, 8, 11 IN ADDITION TO THE |
| PREVIOUS COMMENTS. |
| |
| 47.) THE SIDE ELEVATION DOES NOT |
| COMPLY WITH TABLE 600 (TYPE |
| IV, 10-20' IS LIMITED TO 20% OF |
| OPENINGS). |
| |
| 48.) PROVIDE PRODUCT INFORMATION FOR |
| THE 4 HOUR BLOCK REFERENCED UL901, SHEET |
| A6.SEE NOTE 1, THE CONCRETE BLOCK IS |
| TO BEAR THE UL CLASS MARKING.PLEASE |
| NOTE THAT THIS BLOCK IS NOT READILY |
| AVAILABLE LOCALLY. |
| |
| 49.) IT APPEARS THAT YOU ARE BUILDING |
| ON AN EXISTING WALL.THIS WALL IS |
| INDICATED ON B-A4 AS UL901.PROVIDE |
| A PERMIT NUMBER AND PLANS SHOWING |
| THE EXISTING WALL CONSTRUCTION. RE |
| DETAIL 3-S2.4, SPECIFY EMBEDMENT INTO |
| EXISTING WALL. |
| |
| 50.)THE FOOTING CANNOT ENCROACH |
| THE PROPERTY LINE.ADDRESS. |
| |
| 51.)SHEET S3.9, BUILDING 11, REAR |
| ELEVATION IS INCORRECTLY NOTED AS |
| FRONT ELEVATION. |
| |
| 52.)FOR BUILDING 10, PRODUCT APPROVALS |
| FOR OUTSWING DOOR W/SIDELITES WAS |
| SUBMITTED; CANNOT LOCATE THIS PRODUCT |
| ON THE PLAN. |
| |
| THE FOLLOWING COMMENT APPLIES TO BLDG |
| 6 ONLY |
| |
| 53.)SECTION 2-A5 SHOWS THE 3RD FLOOR |
| HOLLOW CORE PLANKS AS NOT BEARING ON |
| THE WALL.CLARIFY. |
| |
| THE FOLLOWING COMMENTS APPLIES TO UNIT |
| 36, BUILDING 10 ONLY |
| |
| 54.)THE FIRST FLOOR DEN IS CONSIDERED |
| A BEDROOM BY FBC CHAPTER 13 DEFINITIONS. |
| PLEASE RELABEL THIS ROOM. |
| |
| 55.)SHOW A FIREBLOCKING DETAIL BETWEEN |
| ETIENNE AND MARSEILLE (OVERHANG |
| ENCROACHES THE PROPERTY LINE). |
| |
| 56.)PROVIDE A COPY OF THE PEDESTRIAN/ |
| UTILITY EASEMENT.PLEASE NOTE THAT |
| PLAN REVIEW WILL INCLUDE CONFIRMING THAT |
| THE PLANS CONFORM TO ALL OF THE |
| REQUIREMENTS OF THE EASEMENT AND ZONING |
| APPROVAL, INCLUDING ACCESS AND LIGHTING. |
| |
| 57.)THE LEFT SIDE OF THE PLAN IS NOT |
| READABLE BECAUSE OF THE WAY IT IS |
| STAPLED.PLEASE ENSURE THAT ALL PLANS |
| ARE ENTIRELY READABLE. (SEE SHEET U2) |