2004-07-20 00:00:00DENIED:"BORDEAUX MODEL" END-UNIT
 1.PLEASE NOTE, PER 2001 FBC(M) 104.2.1
 EACH PERMIT APPLICATION REQUIRES 2
 COPIES OF PLANS AND SPECIFICATIONS.
 PLEASE PROVIDE ADDITIONAL COPIES.
  
 2.RETURN AIR JUMPERS FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.PER THE
 REVISED 2001 FBC(M) 601.4 EXCEPTION #1;
 TRANSFER DUCTS SHALL BE A MINIMUM OF 1
 1/2 TIMES THE SQUARE INCHES OF THE
 SUPPLY AIR TO THAT SPACE.EXCEPTION #3;
 ALL AIR INTO THE MASTER SUITE TO BE
 INCLUDED.SEE THE ATTACHED SCHEDULE FOR
 PROPER SIZING FOR THE RETURN AIR JUMPERS
  
 3.PLEASE CLARIFY THE RATING OF THE
 SEPARATION WALL BETWEEN THE GARAGE AND
 THE RESIDENCE.
  
 4.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2, 402.2.1 OR 403.3.
  
 5.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 6.PLANS ARE TO BE SIGNED AND DATED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES AND THE FLORIDA
 ADMINISTRATION CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.