Plan Review Notes For Permit 04060879 |
Permit Number |
04060879 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-20 00:00:00 | DENIED: | | 1.PLEASE NOTE, PER 2001 FBC(M) 104.2.1 | | EACH PERMIT APPLICATION REQUIRES 2 | | COPIES OF PLANS AND SPECIFICATIONS. | | PLEASE PROVIDE ADDITIONAL COPIES. | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS PER | | 2001 FBC(M) 402.2, 402.2.1 OR 403.3. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 4.PLANS ARE TO BE SIGNED AND DATED BY | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | FLORIDA STATUTES AND THE FLORIDA | | ADMINISTRATIVE CODE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|