Plan Review Notes For Permit 04060878 |
Permit Number |
04060878 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-11-24 00:00:00 | DENIED:BUILDING 1 UNIT 6 | | MONACO END UNIT | | 1.THE RETURN AIR JUMPER FROM THE | | MASTER SUITE IS NOT SIZED IN ACCORDANCE | | WITH THE 2001 FBC(M) 601.4 EXCEPTION #1 | | & 3.ALL SUPPLY AIR INTO THE MASTER | | SUITE IS TO BE INCLUDED FOR THE TOTAL | | AIR.RETURN AIR SHALL BE A MINIMUM OF | | 16".PLEASE REVISE PLAN SHEET M-2. | | | | 2.PLEASE NOTE, ON PLAN SHEET M-2 THE | | EXHAUST FAN SCHEDULE INDICATES EF-2 & | | EF-3 WHICH ARE NOT IDENTIFIED ON THE | | PLAN. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|