Plan Review Notes
Plan Review Notes For Permit 04060878
Permit Number 04060878
Review Stop M
Sequence Number 2
Notes
Date Text
2004-11-24 00:00:00DENIED:BUILDING 1 UNIT 6
 MONACO END UNIT
 1.THE RETURN AIR JUMPER FROM THE
 MASTER SUITE IS NOT SIZED IN ACCORDANCE
 WITH THE 2001 FBC(M) 601.4 EXCEPTION #1
 & 3.ALL SUPPLY AIR INTO THE MASTER
 SUITE IS TO BE INCLUDED FOR THE TOTAL
 AIR.RETURN AIR SHALL BE A MINIMUM OF
 16".PLEASE REVISE PLAN SHEET M-2.
  
 2.PLEASE NOTE, ON PLAN SHEET M-2 THE
 EXHAUST FAN SCHEDULE INDICATES EF-2 &
 EF-3 WHICH ARE NOT IDENTIFIED ON THE
 PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  