Plan Review Notes For Permit 04060878 |
Permit Number |
04060878 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-20 00:00:00 | DENIED:"MONACO MODEL" END-UNIT | | 1.RETURN AIR JUMPER FROM THE MASTER | | BEDROOM IS NOT SIZED PROPERLY.PER THE | | REVISED 2001 FBC(M) 601.4 EXCEPTION #1; | | TRANSFER DUCTS SHALL BE A MINIMUM OF 1 | | 1/2 TIMES THE SQUARE INCHES OF THE | | SUPPLY AIR TO THAT SPACE.EXCEPTION #3; | | ALL AIR INTO THE MASTER SUITE IS TO BE | | INCLUDED.SEE THE ATTACHED SCHEDULE FOR | | PROPER SIZING OF THE RETURN AIR JUMPERS. | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS PER | | 2001 FBC(M) 402.2, 402.2.1 OR 403.3. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 4.PLANS ARE TO BE SIGNED AND DATED BY | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | THE HVAC SYSTEM IN ACCORDANCE WITH THE | | FLORIDA STATUTES AND THE FLORIDA | | ADMINISTRATIVE CODE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|