Plan Review Notes
Plan Review Notes For Permit 04060876
Permit Number 04060876
Review Stop M
Sequence Number 1
Notes
Date Text
2004-07-19 00:00:00DENIED:
 1.PLEASE CLARIFY RATING OF THE
 SEPARATION WALL BETWEEN THE GARAGE AND
 THE RESIDENCE.PLEASE NOTE, PLAN SHEET
 M-5 8" FLEX DUCT PENETRATES THE
 SEPARATION BETWEEN THE GARAGE & DEN.
  
 2.RETURN AIR JUMPERS FROM BOTH MASTER
 BEDROOMS ARE NOT SIZED PROPERLY.PER
 THE REVISED 2001 FBC(M) 601.4 EXCEPTION
 #1; TRANSFER DUCTS SHALL BE A MINIMUM OF
 1 1/2 TIMES THE SQUARE INCHES OF THE
 SUPPLY AIR TO THAT SPACE.EXCEPTION #3;
 ALL AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED.SEE THE ATTACHED SCHEDULE FOR
 PROPER SIZING OF RETURN AIR JUMPERS.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PROVIDE OUTSIDE AIR CALCULATIONS
 PER 2001 FBC(M) 402.2 & 402.2.1 OR 403.3
  
 5. PLANS ARE TO BE SIGNED & DATED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN OF THE
 HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES & THE FLORIDA
 ADMINISTRATIVE CODES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved