Plan Review Notes For Permit 04060876 |
Permit Number |
04060876 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-19 00:00:00 | DENIED: | | 1.PLEASE CLARIFY RATING OF THE | | SEPARATION WALL BETWEEN THE GARAGE AND | | THE RESIDENCE.PLEASE NOTE, PLAN SHEET | | M-5 8" FLEX DUCT PENETRATES THE | | SEPARATION BETWEEN THE GARAGE & DEN. | | | | 2.RETURN AIR JUMPERS FROM BOTH MASTER | | BEDROOMS ARE NOT SIZED PROPERLY.PER | | THE REVISED 2001 FBC(M) 601.4 EXCEPTION | | #1; TRANSFER DUCTS SHALL BE A MINIMUM OF | | 1 1/2 TIMES THE SQUARE INCHES OF THE | | SUPPLY AIR TO THAT SPACE.EXCEPTION #3; | | ALL AIR INTO THE MASTER SUITE SHALL BE | | INCLUDED.SEE THE ATTACHED SCHEDULE FOR | | PROPER SIZING OF RETURN AIR JUMPERS. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 4.PROVIDE OUTSIDE AIR CALCULATIONS | | PER 2001 FBC(M) 402.2 & 402.2.1 OR 403.3 | | | | 5. PLANS ARE TO BE SIGNED & DATED BY THE | | PERSON RESPONSIBLE FOR THE DESIGN OF THE | | HVAC SYSTEM IN ACCORDANCE WITH THE | | FLORIDA STATUTES & THE FLORIDA | | ADMINISTRATIVE CODES. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|