Plan Review Notes For Permit 04060876 |
Permit Number |
04060876 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-24 00:00:00 | ************ UNSAT ************* | | BLDG #12 | | | | 1)NOTE; PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH THE SUBMITTED | | PANEL SCHEDULE. | | | | 2)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR | | SD LOCATIONS. 3'FROM BATHS/KITCHENS AND | | SUPPLY AIR. 5'RA, 20' FRO COOKING APPL | | W/ EXCEPTIONS. | | | | 3)NOTE: PLEASE SHOW A/C CU DISC'S 440.11 | | | | 4)NOTE: PLEASE SEE MISPRINT FOR 210.12 | | 2002 NEC | | | | 5)NOTE: PLEASE SEE LOAD CALCULATIONS | | SHOWS CU LOAD AS BEING GREATER THAN | | AHU HEAT? PLEASE CORRELATE WITH MECH | | PLANS. | | | | 6)NOTE: PLEASE SEE FAC61G15-23.002, | | FS 471.023 | | PLEASE INCLUDE ALL REQUIRED LICENSE | | #'S ON TITLE BLOCKS. | | PLEASE SEE FIRM SHOWN ON TITLE BLOCK | | SHOWS AS HAVING A "CLOSED" LICENSE ON | | DBPR WEBSITE. PLEASE SEE ATTACHED COPY. | | REQUIRED ON ALL SHEETS AND FOR ALL | | TRADES WHEATHER OR NOT COMMENT IS MADE | | FROM THAT REVIEWER. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|