Plan Review Notes
Plan Review Notes For Permit 04060876
Permit Number 04060876
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-24 00:00:00************ UNSAT *************
 BLDG #12
  
 1)NOTE; PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 SD LOCATIONS. 3'FROM BATHS/KITCHENS AND
 SUPPLY AIR. 5'RA, 20' FRO COOKING APPL
 W/ EXCEPTIONS.
  
 3)NOTE: PLEASE SHOW A/C CU DISC'S 440.11
  
 4)NOTE: PLEASE SEE MISPRINT FOR 210.12
 2002 NEC
  
 5)NOTE: PLEASE SEE LOAD CALCULATIONS
 SHOWS CU LOAD AS BEING GREATER THAN
 AHU HEAT? PLEASE CORRELATE WITH MECH
 PLANS.
  
 6)NOTE: PLEASE SEE FAC61G15-23.002,
 FS 471.023
 PLEASE INCLUDE ALL REQUIRED LICENSE
 #'S ON TITLE BLOCKS.
 PLEASE SEE FIRM SHOWN ON TITLE BLOCK
 SHOWS AS HAVING A "CLOSED" LICENSE ON
 DBPR WEBSITE. PLEASE SEE ATTACHED COPY.
 REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 FROM THAT REVIEWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]