Notes
Date Text
2004-11-17 00:00:00DENIED: ENTIENNE/MARSIELLE/VEZELAY
 UNITS
  
 1.COMMENT #3 FROM REVIEW DATED 7-19-04
 WAS NOT ADDRESSED.PLEASE CLARIFY THE
 RATING BETWEEN THE GARAGE AND THE
 RESIDENCE.PROVIDE DETAIL.
  
 2.FAN SCHEDULE INDICATED ON PLAN
 SHEETS M-6, M-7, & M-8 INDICATES EF-3
 FOR THE GARAGE WHICH IS NOT INDICATED ON
 THE PLAN.PLEASE CLARIFY.
  
 PLAN SHEET M-8 VEZELAY-END UNIT, THE
 EQUIPMENT SCHEDULEINDICATES A
 NONPROGRAMMABLE THERMOSTAT.THE ENERGY
 CALCULATIONS SHOW A PROGRAMMABLE
 THEROSTAT CREDIT.PLEASE REVISE THE
 EQUIPMENT SCHEDULE TO CORRELATE WITH THE
 ENERGY CALCULATIONS.
  