2004-07-19 00:00:00 | DENIED:"VEZELAY MODEL" | | 1.PROVIDE OUTSIDE AIR CALCULATIONS PER | | 2001 FBC(M) 402.2, 402.2.1 OR 403.3. | | | | 2.AUXILAIRY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 3.PLAN SHEET M-8 INDICATES FLEX DUCT | | PENETRATING SEPARATION WALL BETWEEN THE | | GARAGE & RESIDENCE.PLEASE INDICATE THE | | RATING OF THESE WALLS. | | | | 4.PLANS ARE TO BE SIGNED AND DATED BY | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | THE HVAC SYSTEM IN ACCORDANCE WITH THE | | FLORIDA STATUTES AND THE FLORIDA | | ADMINISTRATIVE CODE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|