Plan Review Notes
Plan Review Notes For Permit 04060871
Permit Number 04060871
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-06-23 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES REQUIRED.
  
 3) PRESCRIPTVE STRENGTH REQUIREMENTS
 SHALL BE SHOWN ON PLANS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 4) IS THE DOOR BETWEEN THE THE GARAGE
 AND THE STAIRS RATED. NO RATING SHOWN
 ON DOOR SCHEDULE.
  
 5) SMOKE DETECTORS SHALL BE PLACED
 A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 6) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PAGE A.1 INDICATES THAT
 THE BUILDING WILL BE FIRE SPRINKLER
 PROTECTED.
  
 7) NO INFORMATION PROVIDED REGARDING
 MONITORING OF THE FIRE SPRINKLER SYSTEM.
  
 8) SITE PLAN DOES NOT DISPLAY ANY
 FIRE HYDRANTS.
  
 9) NO MENTION OF ANY FIRE EXTINGUISHERS.
  
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL