Plan Review Notes
Plan Review Notes For Permit 04060871
Permit Number 04060871
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-24 00:00:00*************** UNSAT ***************
 BLDG # 10
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE MISPRINT FOR NEC
 210.12, 2002 NEC.
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 SD LOCATIONS. 3'FROM BATHS/KITCHENS,
 SUPPLY GRILLES.5' FROM RA GRILLES, 20'
 FROM COOKING APPLIANCES. W/ EXCEPTIONS.
  
 4)NOTE:PLEASE SEE OCP SHOWN FOR AHU IS
 SHOWN MUCH LARGER THAN CU OCP, YET
 LOAD CALCS SHOW CU LOAD AS GREATER LOAD?
 PLEASE CORRELATE WITH MECH PLANS AND
 ANY QUESTIONS ON SIZE OF HEAT KW FOR
 THIS SIZE UNIT.
  
 5)NOTE: PLEASE SHOW DICONNECT AND LOCAT-
 -IONS ON ELECTRICAL PLANS. 440.11
  
 6)NOTE: PLEASE SEE FIRM SHOWN ON TITLE
 BLOCK, FRIM'S LICENSE # IS COMING UP
 AS CLOSED ON THE STATE DBPR WEBSITE.
 PLEASE INCLUDE ALL REQUIRED LICENSE #'S
 ON TITLE BLOCK PER 61G15-23.002
 FS 471.023
 PLEASE SEE # IS NOT SHOWN AT THIS TIME.
 THIS IS REQUIRED FOR ALL SHEETS AND ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWERS.
  
 PLEASE SEE NOTES FROM OTHER REVIEWS AS
 THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  