Date |
Text |
2004-06-24 00:00:00 | *************** UNSAT *************** |
| BLDG # 10 |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULE. |
| |
| 2)NOTE: PLEASE SEE MISPRINT FOR NEC |
| 210.12, 2002 NEC. |
| |
| 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR |
| SD LOCATIONS. 3'FROM BATHS/KITCHENS, |
| SUPPLY GRILLES.5' FROM RA GRILLES, 20' |
| FROM COOKING APPLIANCES. W/ EXCEPTIONS. |
| |
| 4)NOTE:PLEASE SEE OCP SHOWN FOR AHU IS |
| SHOWN MUCH LARGER THAN CU OCP, YET |
| LOAD CALCS SHOW CU LOAD AS GREATER LOAD? |
| PLEASE CORRELATE WITH MECH PLANS AND |
| ANY QUESTIONS ON SIZE OF HEAT KW FOR |
| THIS SIZE UNIT. |
| |
| 5)NOTE: PLEASE SHOW DICONNECT AND LOCAT- |
| -IONS ON ELECTRICAL PLANS. 440.11 |
| |
| 6)NOTE: PLEASE SEE FIRM SHOWN ON TITLE |
| BLOCK, FRIM'S LICENSE # IS COMING UP |
| AS CLOSED ON THE STATE DBPR WEBSITE. |
| PLEASE INCLUDE ALL REQUIRED LICENSE #'S |
| ON TITLE BLOCK PER 61G15-23.002 |
| FS 471.023 |
| PLEASE SEE # IS NOT SHOWN AT THIS TIME. |
| THIS IS REQUIRED FOR ALL SHEETS AND ALL |
| TRADES WHEATHER OR NOT COMMENT IS MADE |
| BY OTHER REVIEWERS. |
| |
| PLEASE SEE NOTES FROM OTHER REVIEWS AS |
| THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |