Plan Review Notes For Permit 04060869 |
Permit Number |
04060869 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-11-17 00:00:00 | DENIED: ETIENNE/MARSIELLE/VEZELAY UNTIS | | 1.COMMENT #3 FROM REVIEW DATED | | 7-19-04 | | WAS NOT ADDRESSED.PLEASE CLARIFY THE | | RATING BETWEEN THE GARAGE AND THE | | RESIDENCE.PROVIDE DETAIL. | | | | 2.FAN SCHEDULE INDICATED ON PLAN | | SHEETS M-6, M-7, & M-8 INDICATES EF-3 | | FOR THE GARAGE WHICH IS NOT INDICATED | | ON | | THE PLANS. | | | | 3.PLAN SHEET M-8 VEZELAY-END UNIT - | | THE EQUIPMENT SCHEDULE FOR THE CU & | | AHU, | | SCHEDULE INDICATES A NONPROGRAMMABLE | | THERMOSAT.THE ENERGY CALCULATIONS | | SHOW | | A PROGRAMMABLE THERMOSAT CREDIT. | | PLEASE | | REVISE THE EQUIPMENT SCHEDULE TO | | CORRELATE WITH THE ENERGY CALCULATIONS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS @ (561)805-6719. |
|