Plan Review Notes
Plan Review Notes For Permit 04060868
Permit Number 04060868
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P.4 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENT, THE TUB IN
 BATH 2 THIRD FLOOR IS NOT VENTED. THE
 TUB SHALL CONNECT TO THE BRANCH DRAIN
 DOWNSTREAM OF THE LAV. SEC. 901.2.1.
 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]