2005-01-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 COMMENTS APPLY TO 04060867, 04060868
 04060856, 04060855, 04060842, 04060786,
 04060869, 04060871, 04060873
  
 COMMENTS 1, 2, 4,5,7 AND 12 APPLY TO
 04060880, 04060882
  
 COMMENTS 1, 2, 4, 5, 6 AND 12 APPLY TO
 04060876, 04060877
  
 1.)SUBCONTRACTORS HAVE SIGNED ONTO
 THE
 PERMIT SUBSEQUENT TO PERMIT INTAKE.
 PLEASE COORDINATE ASSIGNING OF THE
 SUBCONTRACTORS AND SUB PERMIT
 NUMBERS WITH DEAN RUNNELS, 805-6681 TO
 AVOID DELAYS AT TIME OF ISSUANCE.NOTE
 THAT AT THIS TIME THE ROOF PERMIT
 CANNOT BE ISSUED BECAUSE THE PRODUCT
 APPROVALS SUBMITTED ARE NOT COMPLIANT
 WITH THE PLAN (LIMITATION OF 33'.
  
 2.)THE FOOTINGS AND PORCH CANNOT
 ENCROACH THE PROPERTY LINE.
  
 3.)THE EXISTING RETAINING WALL CANNOT
 BE USED AS THE EXTERIOR BEARING WALL AS
 PER BUILDING OFFICIAL.
  
 4.)2-A6, THE STAIR RAIL SERVES AS A
 GUARDRAIL AND IS REQUIRED TO BE A
 MINIMUM OF 36" FBC1015.
  
 5.)B-A7 HAS BEEN REPLACED BY AN 8 1/2
 X 14 DETAIL; PLEASE CROSS OFF THE
 NONCOMPLIANT DETAIL WHICH IS STILL ON
 THE PLAN.
  
 6.)REGARDING THE ENGINEER'S LETTER
 FOR
 THE ROOF SHINGLES, PURSUANT TO FAC9B-72
 A FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL IS REQUIRED.SUBMIT AN
 APPLICATION AS REQUESTED WITH
 APPROPRIATE ENGINEERING.SUBJECT TO
 APPROVAL BY ASSISTANT BUILDING
 OFFICIAL.THE LETTER PREPARED BY DAVID
 SHUMATE, PE DATED 12/16/04 STATING THE
 DESIGN PRESSURE OF THE SHINGLES AND THE
 DP OF THE JOB DOES NOT PROVIDE ENOUGH
 DATA FOR ISSUANCE OF LOCAL PRODUCT
 APPROVAL (CONFIRMED WITH BUILDING
 OFFICIAL).ALSO NOTE THAT THE LETTER
 REFERS TO A MEAN ROOF HEIGHT OF 34',
 BUT
 BUILDING 8 HAS A MEAN ROOF HEIGHT OF
 34'4"+.
  
 LOCAL PRODUCT APPROVAL CAN BE REVIEWED
 AND ISSUED SEPARATELY FROM THE
 RESUBMITTAL PROCESS.
  
 7.)3-A4 (NEW DETAIL )REFERS TO
 UBC1988
 WHICH IS NOT THE APPLICABLE BUILDING
 CODE.PROVIDE EITHER AN APPROVED
 ASSEMBLY LISTING OR CALCULATED FIRE
 RESISTANCE, FBC CHAPTER 7.
  
 8.)THE REVISION TO PERMIT #01091727
 (THE EXISTING RETAINING WALL) CONTAINS
 A LETTER FROM JENKINS & CHARLAND DATED
 10/9/01 IN REGARDS TO THE REDESIGN OF
 THE RETAINING WALL TO BE USED ALSO AS
 THE EXTERIOR BEARING WALL OF THE
 TOWNHOUSES.PROVIDE THE ORIGINAL
 SEALED
 CALCULATIONS REFERRED TO IN THAT
 LETTER.
 ALL DELEGATED ENGINEERING IS TO BE
 REVIEWED BY EOR.
  
 9.)WEEPHOLES WERE PLACED IN THE
 EXISTING WALL AVOIDING THE TOWNHOUSE
 LOCATIONS, BUT THE TOWNHOUSES WERE
 REPLATTED, CHANGING THE TOWNHOUSE
 LOCATIONS.ADDRESS. SEE RFI WALL 0060
 11/9/01, RFI WALL-0001 7/27/2001 IN THE
 REVISION.
  
 10.) INCORPORATE THE ACTUAL EXISTING
 WALL CONSTRUCTION DETAIL INTO THE PLAN.
 THERE IS A REFERENCE TO THE FOUNDATION
 PLAN 1-A%, WHICH REFERS TO SECTIONS 1
 AND 2 S2.4, WHICH STATE "EXISTING - SEE
 PLAN."
  
 11.)THE EXISTING WALL CONSTRUCTION
 PLANS SHOW ELEVATION CHANGES.IT
 APPEARS THAT THERE MAY BE ELEVATION
 CHANGES IN THE MIDDLE OF THE PROPOSED
 TOWNHOUSE WALLS.HOW DO THE CONTROL
 JOINTS AND ELEVATION CHANGES OF THE
 WALL AFFECT THE TOWNHOUSE STRUCTURE?
  
 12.)A LETTER WAS SUBMITTED IN
 RESPONSE
 TO A PREVIOUS COMMENT IN REGARDS TO
 SHOWING THE ABILITY OF THE HOLLOW CORE
 TO CARRY THE LINE LOAD OF THE BLOCK
 WALLS.PLEASE HAVE THE RESPONSE LETTER
 DATED 12/20/04 PREPARED BY BRADLEY
 CASH, PE (PCSI) SUBMITTED IN ORIGINAL
 FORM, SIGNED AND SEALED FAC61G15-23.002
 INCLUDING PRINTED LICENSE NUMBER.ALSO
 PLEASE ADDRESS THE WEIGHT OF BEAMS, ETC.
 IN THE CALCS AS DISCUSSED WITH BRADLEY
 CASH, PE OF PCSI.
  