2004-06-24 00:00:00 | *************** UNSAT *************** |
| BLDG # 7 |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH SUBMITTED |
| PANLE SCHEDULE. |
| |
| 2)NOTE: PLEASE SEE NFPA-72 FOR SD |
| INSTALLATION LOCATIONS. |
| 3'BATHS,LITS, 20' COOKING ETC. PLEASE |
| ALSO SEE EXCEPTIONS. |
| |
| 3)NOTE: PLEASE SEE MISPRINT FOR ARC |
| FAULT PROETCTION. NEC 210.12 E-8 |
| |
| 4)NOTE: PLEASE SEE CLOSET LT/ FIXTURE |
| TYPE AND DISTANCE FROM SHELVES PER 410.8 |
| |
| 5)NOTE: PLEASE INDICATE A/C CU DISC'S |
| PER 440.11 |
| |
| 6)NOTE: PLEASE SEE FAC 61G15-23.002, |
| FS 471.023 |
| PLEASE INCLUDE ALL LICENSE #'S ON TITLE |
| BLOCK. |
| PLEASE SEE ATTACHED COPY OF DBPR PRINT |
| OUT OF WEB-SITE. FIRM AS SHOWN ON TITLE |
| BLOCK IS SHOWN AS HAVING A "CLOSED" |
| LICENSE #. |
| PLEASE SEE ABOVE IS REQUIRED ON ALL |
| SHEETS AND TITLE BLOCKS WHEATHER OR NOT |
| COMMENT IS MADE BY OTHER REVIEWERS. |
| |
| 7)NOTE: PLEASE SEE OCP FOR AHU IS SHOWN |
| LARGER THAN CU , YET LOAD CALCS SHOW |
| CU LOAD? PLEASE CORRELATE WITH A/C PLANS |
| |
| PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |