2004-11-19 00:00:00DENIED:BUILDING 6 UNIT 28
 MONACO END UNIT
 RETURN AIR FROM THE MASTER BEDROOM IS
 NOT SIZED IN ACCORDANCE WITH THE MINIMUM
 REQUIREMENT OF 2001 FBC(M)601.4
 EXCEPTION #1 AND 3.ALL SUPPLY AIR INTO
 THE MASTER SUITE IS TO BE INCLUDED FOR
 THE TOTAL SUPPLY AIR INTO THAT SPACE.
 RETURN AIR JUMPER IS TO BE 1 1/2 TIMES
 THE TOTAL SQAURE INCHES OF THE TOTAL
 SUPPLY.PLEASE REVISE.
  
 PLEASE NOTE, THE EXHAUST FAN SCHEDULE ON
 PLAN M-2 SHOWS EF-2 & EF-3 FOR THE
 KITCHEN AND GARAGE EXHAUST WHICH ARE NOT
 INDICATED ON THE PLAN.PLEASE CLARIFY.
  