Plan Review Notes For Permit 04060866 |
Permit Number |
04060866 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-11-19 00:00:00 | DENIED:BUILDING 6 UNIT 28 | | MONACO END UNIT | | RETURN AIR FROM THE MASTER BEDROOM IS | | NOT SIZED IN ACCORDANCE WITH THE MINIMUM | | REQUIREMENT OF 2001 FBC(M)601.4 | | EXCEPTION #1 AND 3.ALL SUPPLY AIR INTO | | THE MASTER SUITE IS TO BE INCLUDED FOR | | THE TOTAL SUPPLY AIR INTO THAT SPACE. | | RETURN AIR JUMPER IS TO BE 1 1/2 TIMES | | THE TOTAL SQAURE INCHES OF THE TOTAL | | SUPPLY.PLEASE REVISE. | | | | PLEASE NOTE, THE EXHAUST FAN SCHEDULE ON | | PLAN M-2 SHOWS EF-2 & EF-3 FOR THE | | KITCHEN AND GARAGE EXHAUST WHICH ARE NOT | | INDICATED ON THE PLAN.PLEASE CLARIFY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|