Plan Review Notes
Plan Review Notes For Permit 04060863
Permit Number 04060863
Review Stop M
Sequence Number 1
Notes
Date Text
2004-07-19 00:00:00DENIED:"GENEVA MODEL" MID-UNIT
 1.PLEASE NOTE, ONLY ONE PLAN PER SET
 SUBMITTED FOR REVIEW.PLAN INDICATES
 TWO GENEVA MID-UNITS.THEREFORE TWO
 PLANS WILL BE REQUIRED PER SET.2001
 FBC(M) 104.2.1.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2, 402.2.1 OR 403.3.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PLANS ARE TO BE SIGNED AND DATED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES AND THE FLORIDA
 ADMINISTRATION CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved