2004-06-24 00:00:00************* UNSAT ******************
 BLDG # 6
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE:PLEASE SEE NFPA-72 8-1.4.2 FOR
 LOCATIONS OF SD'S.
  
 3)NOTE: PLEASE SEE MISPRINT OF 210.12
 FROM 2002 NEC
  
 4)NOTE: PLEASE SHOW A/C CU DISCONNECTS
 PER 440.11
  
 5)NOTE: PLEASE LOAD CALCUALTIONS INDI-
 -CATE CU LARGER THAN AHU HEAT?
 OCP FOR AHU IS SHOWN MUCH LARGER THAN
 CU??
 PLEASE CORRELATE WITH MECH PLANS.
  
 6)NOTE: PLEASE SEE MISSING LICENSE #'S
 REQUIRED TO BE LOCATED ON TITLE BLOCK
 PER FAC 61G15-23.002
 FS 471.023
 PLEASE SEE FIRM SHOWN ON PLAN HAS A
 CLOSED LICENSE WITH THE STATE DBPR.
 PLEASE SEE ATTACHED COPY OF PRINT OUT
 FROM STATE WEBSITE.
 THIS IS REQUIRED FOR ALL SHEETS AND
 TRADES.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWS
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  