2005-07-05 00:00:00****CORRECTIONS****
 TRUSS SUBMITTALS, BUILDINGS 1 - 12
 PREPARED BY MORRIS SHASHOUA, PE
  
 1.)THE DRAWINGS WERE NOT APPROVED BY
 EOR; HE HAS CHECKED THE BOX WHICH STATES
 "REVISE AND RESUBMIT".
  
 2.)DOCUMENTS PREPARED BY AND ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G15-23.002.
  
 3.)BCLL IS TO COMPLY WITH FBC TABLE
 1605.1, MINIMUM OF 10# FOR ATTICS WITH
 NO STORAGE, 30# FOR ATTICS WITH STORAGE.
  
 4.)THE DESIGN CRITERIA ON THE TRUSS
 LAYOUT DRAWING AND THE TRUSS ENGINEERING
 IS NOT CONSISTENT WITH THE CRITERIA
 SPECIFIED BY EOR (SHEET S0.1).EITHER
 REVISE THE PLAN OR CHANGE THE TRUSS
 DESIGN CRITERIA.
  