2004-07-20 00:00:00DENIED:"GENEVA MODEL" END-UNIT
 1.PROVIDE OUTSIDE AIR CALCUALTIONS PER
 2001 FBC(M) 402.2, 402.2.1 OR 403.3.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 3.PLANS ARE TO BE SIGNED AND DATED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES AND THE FLORIDA
 ADMINISTRATIVE CODE.
  