Plan Review Notes For Permit 04060859 |
Permit Number |
04060859 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-20 00:00:00 | DENIED:"GENEVA MODEL" END-UNIT | | 1.PROVIDE OUTSIDE AIR CALCUALTIONS PER | | 2001 FBC(M) 402.2, 402.2.1 OR 403.3. | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 3.PLANS ARE TO BE SIGNED AND DATED BY | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | THE HVAC SYSTEM IN ACCORDANCE WITH THE | | FLORIDA STATUTES AND THE FLORIDA | | ADMINISTRATIVE CODE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|