2004-06-24 00:00:00 | *************** UNSAT ************ |
| BLDG. #1 |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULE. |
| |
| 2)NOTE: PLEASE SEE NFPA-72 FOR SD |
| LOCATIONS. 3'FROM BATHS/KITCHENS, 5' |
| FROM RA GRILLES, 3' SUPPLY, 20' |
| FROM COOKING APPLIANCES W/ EXCEPTIONS. |
| 8-1.4.2 |
| |
| 3)NOTE: PLEASE SHOW DISC'S FOR A/C CU'S. |
| 440.11 |
| |
| 4)NOTE: PLEASE SEE MISPRINT FOR 210.12 |
| ARC FAULT IS UNDER 2002 NEC. |
| |
| 5)NOTE: PLEASE SEE OCP FOR AHU IS SHOWN |
| MUCH LARGER THAN OCP FOR CU, YET LOAD |
| ON LOAD CALCS REFER TO CU LOAD? |
| PLEASE CORRELATE WITH MECH PLANS FOR |
| A HOUSE THIS SIZE. |
| |
| 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| FS 471.023. PLEASE INCLUDE ALL REQUIRED |
| LICENSE #'S ON TITLE BLOCK. |
| PLEASE SEE FIRM SHOWN ON TITLE BLOCK |
| NOW IS SHOWN AS HAVING A "CLOSED" |
| LICENSE WITH STATE DBPR. |
| SEE ATTACHED PRINT OUT. |
| |
| PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| WHICH MAY AFFECT ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |