Plan Review Notes
Plan Review Notes For Permit 04060859
Permit Number 04060859
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-24 00:00:00*************** UNSAT ************
 BLDG. #1
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE NFPA-72 FOR SD
 LOCATIONS. 3'FROM BATHS/KITCHENS, 5'
 FROM RA GRILLES, 3' SUPPLY, 20'
 FROM COOKING APPLIANCES W/ EXCEPTIONS.
 8-1.4.2
  
 3)NOTE: PLEASE SHOW DISC'S FOR A/C CU'S.
 440.11
  
 4)NOTE: PLEASE SEE MISPRINT FOR 210.12
 ARC FAULT IS UNDER 2002 NEC.
  
 5)NOTE: PLEASE SEE OCP FOR AHU IS SHOWN
 MUCH LARGER THAN OCP FOR CU, YET LOAD
 ON LOAD CALCS REFER TO CU LOAD?
 PLEASE CORRELATE WITH MECH PLANS FOR
 A HOUSE THIS SIZE.
  
 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023. PLEASE INCLUDE ALL REQUIRED
 LICENSE #'S ON TITLE BLOCK.
 PLEASE SEE FIRM SHOWN ON TITLE BLOCK
 NOW IS SHOWN AS HAVING A "CLOSED"
 LICENSE WITH STATE DBPR.
 SEE ATTACHED PRINT OUT.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]