2004-11-19 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)SEPARATE PERMITS REQUIRED FOR |
| TRADES. |
| |
| 3.)SIGN THE OWNER/AGENT LINE OF |
| THE ENERGY CALC. |
| |
| 4.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE |
| STAMPED AND THE RECEIPT ATTACHED TO THE |
| APPLICATION.233-5025 |
| |
| 5.)SEE PREVIOUS LIST, ITEM #14. |
| PROVIDE A SURVEY FOR THIS PROPERTY. |
| |
| 6.)THE PLANS AND ENERGY CALCS SHOW |
| THE COMMON WALL (REFERRED TO AS AN |
| ADJACENT WALL, LINE 9B) AS HAVING AN R |
| VALUE OF 8.4.YOU CANNOT INCLUDE |
| INSULATION IN ANOTHER UNIT.REVISE TO |
| REFER TO CORRECT WALL TYPE (COMMON) AND |
| R VALUE (4.2). |
| |
| 7.)THE WALL SEPARATING THE TWO UNITS |
| IS TO BE CONTINUOUS THROUGH THE FRONT |
| PORCH.FBC704.4.2. (NEW COMMENT; NOT |
| ON |
| PREVIOUS LIST.) |
| |
| 8.)SEE PREVIOUS LIST, ITEM #32, |
| WINDOW BUCK TO GIVE FULL SUPPORT OF THE |
| WINDOW, FBC1707.4.4.2 (A7). |
| |
| 11.)SEE PREVIOUS LIST, ITEM #50, |
| FOOTING CANNOT ENCROACH PROPERTY LINE, |
| DETAILS B-A4, 1-A5, ANY OTHER |
| APPLICABLE |
| DETAILS. |
| |
| 12.)S0.1, ITEM #4, DECLARES THIS |
| BUILDING AS A SIMPLE DIAPHRAGM. |
| FBC1606.1.5, THE MEAN ROOF HEIGHT |
| (>34') CANNOT EXCEED THE LEAST |
| HORIZONTAL DIMENSION (33'), A3 |
| ELEVATIONS.FOR COMPONENTS AND |
| CLADDING, SAYS "SEE PLAN"; WHERE? |
| |
| 13.)THE 2 HR TENANT SEPARATION WALL |
| IS |
| TO MAINTAIN THE STRUCTURAL INTEGRITY |
| AND |
| FIRE RESISTANCE INDEPENDENT OF THE UNIT |
| ON THE OPPOSITE SIDE OF THE WALL, |
| FBC704.4.2.DETAIL 9-S2.2 SHOWS A |
| REINFORCED CONCRETE TOPPING WHICH ENDS |
| AT THE TENANT SEPARATION WALL |
| (ACCEPTABLE).DETAIL 2-A5 SHOWS THIS |
| TOPPING AS CONTINUOUS THROUGH THE WALL. |
| DETAILS SHOULD BE CONSISTENT.IF |
| DETAIL |
| 2-A5 IS USED, WHERE DOES THE |
| REINFORCEMENT FOR THE CONCRETE TOPPING |
| END? |
| |
| 14.)16-S2.3 (???APPEARS TO BE 2.3, |
| BUT |
| THE SHEET NUMBER ON THE PLAN IS NOT |
| CLEAR) SHOWS A WOOD POST, WOOD BEAM FOR |
| THE FRONT PORCH.B-A4 SHOWS A TS |
| COLUMN |
| W/STUCCO, WOOD BEAM.HOW DOES THIS |
| COMPLY WITH THE 1HR PROTECTED |
| REQUIREMENT OF TABLE 600 FOR COLUMNS |
| AND |
| BEAMS?ALSO APPLIES TO 4-S2.3 |
| |
| 15.)PLANS REFER TO FIRE RESISTANT |
| CALCS BY HOLLOW CORE ENGINEER; THESE |
| WERE NOT IN THE PACKAGE, |
| FBC709.2.2.1.2. |
| |
| 16.)STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED FOR ALL CONNECTORS, INCLUDING |
| THE ANGLE FOR THE FLOORS, FAC9B-72. |
| SEE |
| WWW.FLORIDABUILDING.ORG, PRODUCT |
| APPROVAL, FOR MORE INFORMATION. |
| |
| 17.)FBC1007.3.1(1), SUM OF TWO RISERS |
| AND A TREAD TO BE 24-25" (ENTRY |
| VESTIBULE, A2). |
| |
| 18.)SEE 04060897 FOR OTHER COMMENTS |
| APPLICABLE TO THIS BUILDING. |
| |
| |