Plan Review Notes
Plan Review Notes For Permit 04060856
Permit Number 04060856
Review Stop B
Sequence Number 2
Notes
Date Text
2004-11-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEPARATE PERMITS REQUIRED FOR
 TRADES.
  
 3.)SIGN THE OWNER/AGENT LINE OF
 THE ENERGY CALC.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 5.)SEE PREVIOUS LIST, ITEM #14.
 PROVIDE A SURVEY FOR THIS PROPERTY.
  
 6.)THE PLANS AND ENERGY CALCS SHOW
 THE COMMON WALL (REFERRED TO AS AN
 ADJACENT WALL, LINE 9B) AS HAVING AN R
 VALUE OF 8.4.YOU CANNOT INCLUDE
 INSULATION IN ANOTHER UNIT.REVISE TO
 REFER TO CORRECT WALL TYPE (COMMON) AND
 R VALUE (4.2).
  
 7.)THE WALL SEPARATING THE TWO UNITS
 IS TO BE CONTINUOUS THROUGH THE FRONT
 PORCH.FBC704.4.2. (NEW COMMENT; NOT
 ON
 PREVIOUS LIST.)
  
 8.)SEE PREVIOUS LIST, ITEM #32,
 WINDOW BUCK TO GIVE FULL SUPPORT OF THE
 WINDOW, FBC1707.4.4.2 (A7).
  
 11.)SEE PREVIOUS LIST, ITEM #50,
 FOOTING CANNOT ENCROACH PROPERTY LINE,
 DETAILS B-A4, 1-A5, ANY OTHER
 APPLICABLE
 DETAILS.
  
 12.)S0.1, ITEM #4, DECLARES THIS
 BUILDING AS A SIMPLE DIAPHRAGM.
 FBC1606.1.5, THE MEAN ROOF HEIGHT
 (>34') CANNOT EXCEED THE LEAST
 HORIZONTAL DIMENSION (33'), A3
 ELEVATIONS.FOR COMPONENTS AND
 CLADDING, SAYS "SEE PLAN"; WHERE?
  
 13.)THE 2 HR TENANT SEPARATION WALL
 IS
 TO MAINTAIN THE STRUCTURAL INTEGRITY
 AND
 FIRE RESISTANCE INDEPENDENT OF THE UNIT
 ON THE OPPOSITE SIDE OF THE WALL,
 FBC704.4.2.DETAIL 9-S2.2 SHOWS A
 REINFORCED CONCRETE TOPPING WHICH ENDS
 AT THE TENANT SEPARATION WALL
 (ACCEPTABLE).DETAIL 2-A5 SHOWS THIS
 TOPPING AS CONTINUOUS THROUGH THE WALL.
 DETAILS SHOULD BE CONSISTENT.IF
 DETAIL
 2-A5 IS USED, WHERE DOES THE
 REINFORCEMENT FOR THE CONCRETE TOPPING
 END?
  
 14.)16-S2.3 (???APPEARS TO BE 2.3,
 BUT
 THE SHEET NUMBER ON THE PLAN IS NOT
 CLEAR) SHOWS A WOOD POST, WOOD BEAM FOR
 THE FRONT PORCH.B-A4 SHOWS A TS
 COLUMN
 W/STUCCO, WOOD BEAM.HOW DOES THIS
 COMPLY WITH THE 1HR PROTECTED
 REQUIREMENT OF TABLE 600 FOR COLUMNS
 AND
 BEAMS?ALSO APPLIES TO 4-S2.3
  
 15.)PLANS REFER TO FIRE RESISTANT
 CALCS BY HOLLOW CORE ENGINEER; THESE
 WERE NOT IN THE PACKAGE,
 FBC709.2.2.1.2.
  
 16.)STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED FOR ALL CONNECTORS, INCLUDING
 THE ANGLE FOR THE FLOORS, FAC9B-72.
 SEE
 WWW.FLORIDABUILDING.ORG, PRODUCT
 APPROVAL, FOR MORE INFORMATION.
  
 17.)FBC1007.3.1(1), SUM OF TWO RISERS
 AND A TREAD TO BE 24-25" (ENTRY
 VESTIBULE, A2).
  
 18.)SEE 04060897 FOR OTHER COMMENTS
 APPLICABLE TO THIS BUILDING.
  
  