2004-07-20 00:00:00 | DENIED:"BORDEAUX MODEL" END-UNIT |
| 1.PLEASE NOTE, PER 2001 FBC(M) 104.2.1 |
| EACH PERMIT APPLICATION REQUIRES 2 |
| COPIES OF PLANS AND SPECIFICATIONS. |
| PLEASE PROVIDE ADDITIONAL COPIES. |
| |
| 2.RETURN AIR JUMPERS FROM THE MASTER |
| BEDROOM IS NOT SIZED PROPERLY.PER THE |
| REVISED 2001 FBC(M) 601.4 EXCEPTION #1; |
| TRANSFER DUCTS SHALL BE A MINIMUM OF 1 |
| 1/2 TIMES THE SQUARE INCHES OF THE |
| SUPPLY AIR TO THAT SPACE.EXCEPTION #3; |
| ALL AIR INTO THE MASTER SUITE TO BE |
| INCLUDED.SEE THE ATTACHED SCHEDULE FOR |
| PROPER SIZING FOR THE RETURN AIR JUMPERS |
| |
| 3.PLEASE CLARIFY THE RATING OF THE |
| SEPARATION WALL BETWEEN GARAGE AND THE |
| RESIDENCE. |
| |
| 4.PROVIDE OUTSIDE AIR CALCUALTIONS PER |
| 2001 FBC(M) 402.2, 402.2.1 OR 403.3. |
| |
| 5.AUXILIARY DRAIN PAN WITH OVERFLOW |
| PROTECTION REQUIRED PER 2001 FBC(M) |
| 307.2.3. |
| |
| 6.PLANS ARE TO BE SIGNED AND DATED BY |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE HVAC SYSTEM IN ACCORDANCE WITH THE |
| FLORIDA STATUTES AND THE FLORIDA |
| ADMINISTRATIVE CODE. |
| |