Date |
Text |
2004-06-24 00:00:00 | *********** UNSAT *************** |
| BLDG #8 |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULE. |
| |
| 2)NOTE: PLEASE SEE FS 471.023 AND FAC |
| 61G15-23.002. PLEASE INCLUDE REQUIRED |
| LICENSE #'S ON TITLE BLOCK. |
| PLEASE SEE FIRM AS SHOWN ON PLAN IS |
| SHOWN AS LICENSE "CLOSED" ON STATE |
| DBPR. PLEASE SEE PRINT OUT ATTACHED. |
| PLEASE SEE # WAS NOT ON TITLE BLOCK. |
| PLEASE ALSO SEE THIS IS REQUIRED ON |
| ALL SHEETS AND FOR ALL TRADES WHEATHER |
| OR NOT COMMENT IS MADE BY OTHER REVIEWER |
| -S. |
| |
| 3)NOTE: PLEASE SHOW/ INDICATE A/C CU |
| DISC PER 440.11 |
| |
| 4)NOTE: PLEASE SEE 410.8 FOR FIXTURE |
| TYPE AND CLEARENCE FOR MASTER CLOSET. |
| DOES NOTE SEEM TO MEET 410.8 |
| |
| 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU |
| IS MUCH LARGER THAN OCP FOR CU, YET |
| LOAD CALCS SHOW CU LOAD?? |
| PLEASE CORRELATE WITH MECH PLANS. |
| |
| 6)NOTE: PLEASE SEE MISPRINT FOR 210.12 |
| ON E-8 |
| |
| 7)NOTE: PLEASE SEE NFPA-72FOR SD |
| LOCATIONS. 3' FROM BATHS/KITCHENS AND |
| 20' FROM COOKING APPLIANCES. W/ EXCEPT- |
| -IONS. |
| |
| PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |