2004-06-23 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES REQUIRED.
  
 3) PRESCRIPTIVE STRENGTH REQUIREMENTS
 SHALL BE SHOWN ON PLANS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 4) IS THE DOOR BETWEEN THE GARAGE AND
 THE STAIRS RATED. NO RATING SHOWN ON
 DOOR SCHEDULE.
  
 5) SMOKE DETECTORS SHALL BE PLACED A
 MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 6) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PAGE A.1 INDICATES THAT
 THE BUILDING WILL BE FIRE SPRINKLER
 PROTECTED.
  
 7) NO INFORMATION PROVIDED REGARDING
 MONITORING OF THE FIRE SPRINKLER
 SYSTEM.
  
 8) SITE PLAN DOES NOT DISPLAY ANY FIRE
 HYDRANTS.
  
 9) NO MENTION OF ANY FIRE EXTINGUISHERS.
  
 COURTESY REVIEW PERFORMED.
  