Notes
Date Text
2004-06-22 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDGS.
 PLEASE ALSO SEE MISSING EQUIPMENT GROUND
 -ING CONDUCTOR FROM 200A PANEL TO NEW
 100A PANEL.
  
 2)NOTE: PLEASE INDICATE MEANS OF DISC
 AT DEACHED BLDG. 225.31
 MCB?DISCONNECT?
  
 3)NOTE: PLEASE LIST OCP AT 200A PANEL
 FOR NEW FEED.
  
 4)NOTE: PLEASE SEE HEAT SHOWN FOR A/C
 UNIT @ 6500 VA? THIS IS NOT A COMMON
 SIZE, PLEASE VERIFY THIS.
 PLEASE ALSO SEE 424.3B FOR OCP.
  
 5)NOTE: PLEASE SEE 220.31B. PLEASE
 PROVIDE LOAD CALC FOR EXISTING AND NEW.
 215.5
  
 6)NOTE: PLEASE SEE COUNTERSPACE IN
 KITCEHN AREA FOR RECEPT SPACING PER
 210.52C1
  
 7)NOTE: PLEASE INDICATE LT/RECEPT FOR
 ATTIC STORAGE AREA/ AHU. 210.70,210.63
  
 8)NOTE: PLEASE SEE AREA IS CONSIDERED
 AN ADAPTABLE SLEEPING ROOM. ARC FAULT
 PROTECTION WILL BE REQUIRED FOR ALL
 "OUTLETS" IN THAT RM PER 210.12 2002 NEC
 A SD WILL ALSO BE REQUIRED PER NFPA-72
  
 9)NOTE: PLEASE VERIFY IF POOL EQUIPMENT
 SHOWN IS FED FROM A DIFERENT LOCATION?
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  