2004-07-19 00:00:00 | DENIED:"BORDEAUX MODEL" END-UNIT |
| 1.EVERY APPLICATION SUBMITTED FOR |
| REVIEW IS REQUIRED TO HAVE A MINIMUM OF |
| 2 COPIES OF PLANS AND SPECIFICATIONS PER |
| 2001 FBC(M) 104.2.1. |
| |
| 2.RETURN AIR JUMPERS FROM THE MASTER |
| BEDROOM IS NOT SIZED PROPERLY.PER THE |
| REVISED 2001 FBC(M) 601.4 EXCEPTION #1; |
| TRANSFER DUCTS SHALL BE A MINIMUM OF |
| 1 1/2 TIMES THE SQUARE INCHES OF THE |
| SUPPLY AIR TO THAT SPACE.EXCEPTION #3; |
| ALL AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED.SEE THE ATTACHED SCHEDULE FOR |
| PROPER SIZING OF RETURN AIR JUMPER. |
| |
| 2.PLEASE PROVIDE THE RATING OF THE |
| SEPARATION WALL BETWEEN THE GARAGE AND |
| THE RESIDENCE. |
| |
| 3.PROVIDE OUTSIDE AIR CALCULATIONS PER |
| 2001 FBC(M) 402.2, 402.2.1 OR 403.3. |
| |
| 4.AUXILIARY DRAIN PAN WITH OVERFLOW |
| PROTECTION REQUIRED PER 2001 FBC(M) |
| 307.2.3. |
| |
| 5.PLANS ARE TO BE SIGNED AND DATED BY |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE HVAC SYSTEM IN ACCORDANCE WITH THE |
| FLORIDA STATUTES AND THE FLORIDA |
| ADMINISTRATIVE CODE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561) 805-6719. |