Date |
Text |
2004-06-24 00:00:00 | ************* UNSAT **************** |
| |
| 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| AND CORRELATE WITH THE SUBMITTED PANEL |
| SCHEDULE. |
| |
| 2)NOTE: PLEASE SEE MISPRINT FOR REF. |
| OF NEC 210.12. ARC FAULT PROTECTION. |
| |
| 3)NOTE: PLEASE SEE FAC 61G15-23.002, |
| PLEASE INCLUDE ALL LICENSE #'S ON |
| TITLE BLOCK INCLUDING CERTIFICATE OF |
| AUTHORIZATION #. |
| PLEASE ALSO SEE ENGINEERING FIRM SHOWN |
| ON TITLE BLOCK LICENSE IS SHOWING UP |
| ON STATE WEB SITE AS CLOSED. |
| PLEASE SEE ATTACHED COPY FROM DBPR'S |
| SITE. |
| |
| 4)NOTE: PLEASE SHOW DISCONNECT LOCATION |
| ON PLAN FOR A/C CU. 440.11 |
| |
| 5)NOTE: PLEASE SEE 410.8. CLOSET LT |
| TYPE AND LOCATION APPEAR THAT IT WOULD |
| TOO CLOSE TO SHELVEING. |
| |
| 6)NOTE: PLEASE SEE NFPA-72 FOR LOCATION |
| OF SD'S. 8-1.4.2, PLEASE SEE A MIN OF |
| 3' FROM BATH DOORS. 20' FROM COOKING |
| APPLIANCE , W/ EXCEPTIONS. |
| PLEASE NOTE: ON PLANS. |
| |
| PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |