2004-12-03 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)ENTRY VESTIBULE FOR EACH UNIT IS |
| OUTSIDE THE LOT LINE OF THE BUILDING. |
| |
| 3.)SEPARATE PERMITS REQUIRED FOR |
| TRADES. |
| |
| 4.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE |
| STAMPED |
| AND THE RECEIPT ATTACHED TO THE |
| APPLICATION. |
| |
| 5.)ADDITIONAL FEES DUE (VALUE |
| ADJUSTMENT, RADON).SEE ATTACHED. |
| |
| 6.)SUBMIT MULLION PRODUCT APPROVALS. |
| |
| 7.)FLORIDA STATE OR LOCAL PRODUCT |
| APPROVALS REQUIRED FAC9B72. |
| WWW.FLORIDABUILDING.ORG |
| |
| 8.)SIGN THE OWNER/AGENT LINE OF THE |
| ENERGY CALC. |
| |
| 9.)ENERGY CALC 9A SHOULD STATE COMMON |
| WALL, 4.2. |
| |
| 10.) BALCONY GUARDRAIL 3-A6 SHOWS THE |
| POST EMBEDDED IN A CONCRETE SLAB, |
| 10-S2.2 AND FLOOR FRAMING PLAN SHOWS |
| THIS BALCONY AS HOLLOW CORE. |
| |
| 11.)2-A5 SHOWS THE EDGE OF THE HOLLOW |
| CORE BEARING ON THE 2 HR PARTITION |
| BLOCK |
| WALL.SHOW HOW THE STRUCTURAL AND FIRE |
| RESISTANCE IS MAINTAINED PER |
| FBC704.4.2. |
| THIS DETAIL CONFLICTS WITH THE |
| STRUCTURALS (SHOWS CONCRETE TOPPING |
| THROUGH THE WALL). |
| |
| 12.)SEE PREVIOUS LIST, #31, PROVIDE |
| INFORMATION TO SHOW HOW THE HOLLOW CORE |
| PLAN WILL HANDLE THE LINE LOAD OF THE |
| CMU WALLS. |
| |
| 13.)SEE PREVIOUS LIST, #32 WINDOW |
| BUCK |
| TO GIVE FULL SUPPORT OF THE WINDOW, |
| FBC1707.4.4.2 (A7). |
| |
| 14.)A RESIDENT INSPECTOR REQUIRED DUE |
| TO THE SCOPE AND NATURE OF THIS |
| PROJECT. |
| PLEASE CONTACT HAROLD PISKURA. |
| |
| 15.)S0.1, ITEM #4, DECLARES THIS |
| BUILDING AS A SIMPLE DIAPHRAGM. |
| FBC1606.1.5, THE MEAN ROOF HEIGHT |
| (>34') CANNOT EXCEED THE LEAST |
| HORIZONTAL DIMENSION (33'), A3 |
| ELEVATIONS. |
| |
| |
| 16.)PLANS REFER TO FIRE RESISTANT |
| CALCS BY HOLLOW CORE ENGINEER; THESE |
| WERE NOT IN THE PACKAGE, |
| FBC709.2.2.1.2. |
| |
| 17.)SEE PREVIOUS LIST, ITEM #35. |
| WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY |
| SHEETS |
| WHICH HAVE CHANGED.SUBMIT OLD SHEETS |
| SEPARATELY.TO EXPEDITE PLAN REVIEW, |
| SUBMIT A TRANSMITTAL LETTER EXPLAINING |
| HOW EACH ITEM WAS ADDRESSED. |
| |
| 18.)STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED FOR ALL CONNECTORS, INCLUDING |
| THE ANGLE FOR THE FLOORS, FAC9B-72. |
| SEE |
| WWW.FLORIDABUILDING.ORG, PRODUCT |
| APPROVAL, FOR MORE INFORMATION. |
| |
| 19.)FBC1007.3.1(1), SUM OF TWO RISERS |
| AND A TREAD TO BE 24-25" (ENTRY |
| VESTIBULE, A2), LOT 18 ONLY. |
| |
| 20.)PROVIDE A 2 HR FIREBLOCKING DETAIL |
| FOR THE SOFFIT AREA ADJACENT TO THE |
| TENANT SEPARATION 2 HR WALL. |