Plan Review Notes
Plan Review Notes For Permit 04060754
Permit Number 04060754
Review Stop B
Sequence Number 2
Notes
Date Text
2004-12-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)ENTRY VESTIBULE FOR EACH UNIT IS
 OUTSIDE THE LOT LINE OF THE BUILDING.
  
 3.)SEPARATE PERMITS REQUIRED FOR
 TRADES.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 5.)ADDITIONAL FEES DUE (VALUE
 ADJUSTMENT, RADON).SEE ATTACHED.
  
 6.)SUBMIT MULLION PRODUCT APPROVALS.
  
 7.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 8.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 9.)ENERGY CALC 9A SHOULD STATE COMMON
 WALL, 4.2.
  
 10.) BALCONY GUARDRAIL 3-A6 SHOWS THE
 POST EMBEDDED IN A CONCRETE SLAB,
 10-S2.2 AND FLOOR FRAMING PLAN SHOWS
 THIS BALCONY AS HOLLOW CORE.
  
 11.)2-A5 SHOWS THE EDGE OF THE HOLLOW
 CORE BEARING ON THE 2 HR PARTITION
 BLOCK
 WALL.SHOW HOW THE STRUCTURAL AND FIRE
 RESISTANCE IS MAINTAINED PER
 FBC704.4.2.
 THIS DETAIL CONFLICTS WITH THE
 STRUCTURALS (SHOWS CONCRETE TOPPING
 THROUGH THE WALL).
  
 12.)SEE PREVIOUS LIST, #31, PROVIDE
 INFORMATION TO SHOW HOW THE HOLLOW CORE
 PLAN WILL HANDLE THE LINE LOAD OF THE
 CMU WALLS.
  
 13.)SEE PREVIOUS LIST, #32 WINDOW
 BUCK
 TO GIVE FULL SUPPORT OF THE WINDOW,
 FBC1707.4.4.2 (A7).
  
 14.)A RESIDENT INSPECTOR REQUIRED DUE
 TO THE SCOPE AND NATURE OF THIS
 PROJECT.
 PLEASE CONTACT HAROLD PISKURA.
  
 15.)S0.1, ITEM #4, DECLARES THIS
 BUILDING AS A SIMPLE DIAPHRAGM.
 FBC1606.1.5, THE MEAN ROOF HEIGHT
 (>34') CANNOT EXCEED THE LEAST
 HORIZONTAL DIMENSION (33'), A3
 ELEVATIONS.
  
  
 16.)PLANS REFER TO FIRE RESISTANT
 CALCS BY HOLLOW CORE ENGINEER; THESE
 WERE NOT IN THE PACKAGE,
 FBC709.2.2.1.2.
  
 17.)SEE PREVIOUS LIST, ITEM #35.
 WHEN
 RESUBMITTING, PLEASE REPLACE ONLY
 SHEETS
 WHICH HAVE CHANGED.SUBMIT OLD SHEETS
 SEPARATELY.TO EXPEDITE PLAN REVIEW,
 SUBMIT A TRANSMITTAL LETTER EXPLAINING
 HOW EACH ITEM WAS ADDRESSED.
  
 18.)STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED FOR ALL CONNECTORS, INCLUDING
 THE ANGLE FOR THE FLOORS, FAC9B-72.
 SEE
 WWW.FLORIDABUILDING.ORG, PRODUCT
 APPROVAL, FOR MORE INFORMATION.
  
 19.)FBC1007.3.1(1), SUM OF TWO RISERS
 AND A TREAD TO BE 24-25" (ENTRY
 VESTIBULE, A2), LOT 18 ONLY.
  
 20.)PROVIDE A 2 HR FIREBLOCKING DETAIL
 FOR THE SOFFIT AREA ADJACENT TO THE
 TENANT SEPARATION 2 HR WALL.