2004-06-24 00:00:00 | ************ UNSAT ************** |
| BLDG # 4 |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULE. |
| |
| 2)NOTE: PLEASE SEE NFPA-72 FOR SD |
| LOCATIONS. 3' FROM BATHS/KITCHENS AND |
| 20' FROM COOKING APPLIANCES W/ EXCEPTION |
| -S. 8-1.4.2 |
| |
| 3)NOTE: PLEASE INDICATE/SHOW AC, CU |
| DISCONNECTS PER 440.11 |
| |
| 4)NOTE: PLEASE SEE E-8 FOR MISPRINT OF |
| 210.12 FOR ARC FAULT ART. 2002 NEC. |
| |
| 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU |
| IS MUCH LARGER THAN OCP FOR CU, YET |
| LOAD FOR CU IS SHOWN ON LOAD CALCS? |
| PLEASE VERIFY AND CORRELATE WITH |
| MECH PLANS. |
| |
| 6)NOTE: PLEASE SEE FS 471.023, FAC |
| 61G15-23.002 FOR REQUIRED LICENSE #'S |
| ON TITLE BLOCK.PLEASE SEE ATTACHED |
| PRINT-OUT FROM DBPR WHICH INDICATES |
| FIRM AS SHOWN ON TITLE BLOCK AS LICENSE |
| BEING "CLOSED"? |
| PLEASE NOTE, THIS # WAS NOT ON TITLE |
| BLOCK. |
| PLEASE ALSO SEE THE ABOVE IS REQUIRED |
| OF ALL SHEETS AND TRADES WHEATHER OR |
| NOT COMMENT IS MADE FROM OTHER REVIEWERS |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |