Plan Review Notes
Plan Review Notes For Permit 04060721
Permit Number 04060721
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-24 00:00:00************ UNSAT **************
 BLDG # 4
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE NFPA-72 FOR SD
 LOCATIONS. 3' FROM BATHS/KITCHENS AND
 20' FROM COOKING APPLIANCES W/ EXCEPTION
 -S. 8-1.4.2
  
 3)NOTE: PLEASE INDICATE/SHOW AC, CU
 DISCONNECTS PER 440.11
  
 4)NOTE: PLEASE SEE E-8 FOR MISPRINT OF
 210.12 FOR ARC FAULT ART. 2002 NEC.
  
 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU
 IS MUCH LARGER THAN OCP FOR CU, YET
 LOAD FOR CU IS SHOWN ON LOAD CALCS?
 PLEASE VERIFY AND CORRELATE WITH
 MECH PLANS.
  
 6)NOTE: PLEASE SEE FS 471.023, FAC
 61G15-23.002 FOR REQUIRED LICENSE #'S
 ON TITLE BLOCK.PLEASE SEE ATTACHED
 PRINT-OUT FROM DBPR WHICH INDICATES
 FIRM AS SHOWN ON TITLE BLOCK AS LICENSE
 BEING "CLOSED"?
 PLEASE NOTE, THIS # WAS NOT ON TITLE
 BLOCK.
 PLEASE ALSO SEE THE ABOVE IS REQUIRED
 OF ALL SHEETS AND TRADES WHEATHER OR
 NOT COMMENT IS MADE FROM OTHER REVIEWERS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  