Plan Review Notes
Plan Review Notes For Permit 04060563
Permit Number 04060563
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ALL SHEETS A SPACE FOR THE PRINTED
 NAME OF THE PERSON SEALING THE PLANS IS
 REQUIRED. FAC 61G1-16.004(6) & FS 481.
 2055.
 2) SHT A1 SHOW CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES. W/C'S 11-4.16.2,
 LAV'S 11-4.19.3, & KIT. SINK 11-4.24.5.
 3) SHT A1 DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIX-
 TURE. 11-4.22.2.
 4) SHT A1 A DRINKING FOUNTAIN IS REQUIR-
 ED. TABLE 403.1. (SEE SECTION 410.1)
 5) SHT A2 DETAIL D, SHOW SINK HEIGHT AT
 34" MAX. 11-4.24.2, KNEE CLEARANCE 11-4.
 24.3, DEPTH OF SINK 11-4.24.4 AND EX-
 POSED PIPES AND SURFACES 11-4.24.6.
 6) SHT A2 DETAIL "B" SHOW EXPOSED PIPES
 AND SURFACES 11-4.19.4.
 7) SHT P1 WATER RISER DIAGRAM REQUIRED
 SECTION 104.3.1.1. SHOW WATER HAMMER
 ARRESTORS WHERE REQUIRED BY SECTION
 604.9. W.H.A'S SHALL BE LOCATED NEAR THE
 FIXTURES, NOT IN THE CEILING PER PDI-WH
 201.
 8) SHT P1 GENERAL PLUMBING NOTES #17,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE. SECTION 604.9 & SECTION
 104.2.1
 9) ALL SHEETS, PRINTED NAME OF THE ARCH-
 ITECT IS REQUIRED ON TITLE BLOCK. FAC
 61G1-16.004(6) & FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]