Plan Review Notes
Plan Review Notes For Permit 04060563
Permit Number 04060563
Review Stop M
Sequence Number 1
Notes
Date Text
2004-07-01 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 2.INDCIATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL & LAYOUT.
  
 3.DUCT SMOKE DETECTORS IN SYSTEMS THAT
 HAVE THE DESIGN CAPACITY GREATER THAN
 2,000 CFM.2001 FBCF(M) 606.2.1.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER NFPA 90A
 6.4.4.3.
  
 5.PLEASE INDICATE CONDENSATE
 TERMINATION SND LINE SIZE.
  
 6.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.