Plan Review Notes For Permit 04060563 |
Permit Number |
04060563 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-01 00:00:00 | DENIED: | | 1.PLEASE PROVIDE OUTSIDE AIR | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | 2.INDCIATE OUTSIDE AIR INTAKE, DUCT | | SIZE, MATERIAL & LAYOUT. | | | | 3.DUCT SMOKE DETECTORS IN SYSTEMS THAT | | HAVE THE DESIGN CAPACITY GREATER THAN | | 2,000 CFM.2001 FBCF(M) 606.2.1. | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | IN NORMALLY OCCUPIED AREAS PER NFPA 90A | | 6.4.4.3. | | | | 5.PLEASE INDICATE CONDENSATE | | TERMINATION SND LINE SIZE. | | | | 6.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|