Plan Review Notes
Plan Review Notes For Permit 04060563
Permit Number 04060563
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-06-16 00:00:00*************DENIED*********************
 1) WHAT ARE THE WALLS AND CEILINGS
 INTERIOR FINISH CLASSIFICATION? CLASS "A
 "B" OR "C".
  
 2) IT APPEARS THAT ADDITIONAL EXIT SIGN
 AND EMERGENCY LIGHT ARE NEEDED FOR THE
 CORRIDOR LEADING FROM OFFICE #4 TO THE
 RECEPTION AREA.
  
 3) WILL THESE ALTERATIONS AFFECT FIRE
 SPRINKLER COVERAGE AND FIRE ALARM SYSTEM
  
 4) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEM REMODEL.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722