2004-06-15 00:00:00LOAD CALCULATION TO ALSO BE DONE ON
 SERVICE.
  
 LOAD CALCULATIONS IS OK BUT WHEN THE
 NUMBER OF OUTLETS IS KNOWN THEN 180 VA
 EACH IS USED THEN 220.13
  
 RISER SHOWS EAST PANEL TO BE 100A FED
 BY 200A MAIN!
  
 AHU CLOSET ON WEST SIDE NEEDS LIGHT AND
 OUTLET.
  
 NEDD TO SHOW BRASNCH CIRCUIT NUMBERS ON
 THE PLANS FOR THE OUTLETS AND LIGHTS.
  
 PANEL SCHEDULES ARE IDENTICAL SPACES
 ARE OT!!!!!
  
 PAGE E-2 SHOW A SATELITE OUTLET OUTSIDE!
  
 ANY QUESTIONS CALL JAKE LEAHY 805-6740