Date Text
2006-11-01 14:10:35 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 CONDUCTOR IS UNDERSIZED PER 250.66.
 SHOULD BE #1/0 FOR 400 AMP SERVICE (400
 MCM).
  
 2} THE GRC MUST COMPLY WITH 250.50 REF
 250.52.( FOOTER STEEL).AS NOTED ON PERMIT SET.
  
 3} THE ARCHITECT OF RECORD MUST CORRECT, REVISE ,SIGN
 AND SEAL THE PLAN PER 481.221(1)(B)FS.
  
 4} A SMOKE DETECTOR IS REQUIRED BY THE
 STAIRWELL ON THE FIRST FLOOR TO COMPLY
 WITH 905.2.2 FBC.
  
 5} RECEPTACLES ARE REQUIRED TO BE ADDED
 IN THE MASTER SUITE #2 AND BEDROOM #3 TO
 COMPLY WITH 210.52(A)(2)(1). 2'OR MORE
  
 6} THE RECEPTACLE ON THE ISLAND (ALL) MUST BE GFI. SEE
 210.8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]