3 |
|
Notes |
Date |
Text |
2006-11-01 14:10:35 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | CONDUCTOR IS UNDERSIZED PER 250.66. | | SHOULD BE #1/0 FOR 400 AMP SERVICE (400 | | MCM). | | | | 2} THE GRC MUST COMPLY WITH 250.50 REF | | 250.52.( FOOTER STEEL).AS NOTED ON PERMIT SET. | | | | 3} THE ARCHITECT OF RECORD MUST CORRECT, REVISE ,SIGN | | AND SEAL THE PLAN PER 481.221(1)(B)FS. | | | | 4} A SMOKE DETECTOR IS REQUIRED BY THE | | STAIRWELL ON THE FIRST FLOOR TO COMPLY | | WITH 905.2.2 FBC. | | | | 5} RECEPTACLES ARE REQUIRED TO BE ADDED | | IN THE MASTER SUITE #2 AND BEDROOM #3 TO | | COMPLY WITH 210.52(A)(2)(1). 2'OR MORE | | | | 6} THE RECEPTACLE ON THE ISLAND (ALL) MUST BE GFI. SEE | | 210.8(A)(6). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] |
|