Plan Review Notes
Plan Review Notes For Permit 04060548
Permit Number 04060548
Review Stop E
Sequence Number 2
Notes
Date Text
2004-09-17 00:00:00** NOTES REDLINED/REVISE BEFORE ROUGH**
  
 1)NOTE: PLEASE SEE PANELS ARE SHOWN AS
 MLO AND MCB ON RISER.
  
 2)NOTE: NO ARC FAULT PROTECTION PER
 2002 NEC 210.12
  
 3 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 4)NOTE: PLEASE SEE LIGHT REQUIRED AT
 FRONT ENTRANCE/PORCH. LS 101 5-8,
 210.70 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]