Plan Review Notes For Permit 04060548 |
Permit Number |
04060548 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-24 00:00:00 | DENIED: | | 1. MASTER BEDROOM 1ST FLOOR; RETURN AIR | | SHALL BE A MINIMUM OF 16" PER THE | | REVISED 2001 FBC(M) 601.4 EXCEPTION #1 | | AND 3. | | | | 2. MASTER SUITE #2 2ND FLOOR; RETURN | | AIR SHALL BE A MINIMUM OF 14". | | | | 3.RETURN AIR JUMPER FROM THE LIBRARY | | SHALL BE A MINIMUM OF 12". | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. | | | | 4. PLAN DOES NOT INDICATE RETURN AIR | | BACK TO THE AIR HANDLING UNITS.A/C 1 | | SHALL BE DUCTED INTO THE AHU. |
|