 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 CONDUCTOR IS UNDERSIZED PER 250.66.
 SHOULD BE #1/0 FOR 400 AMP SERVICE (400
 MCM).
  
 2} THE GRC MUST COMPLY WITH 250.50 REF
 250.52.( FOOTER STEEL).
  
 3} APPLIANCE CIRCUIT #15 INCORRECTLY
 LISTS A 3 KVA LOAD ON A SINGLE POLE 20
 AMP BREAKER & THE #12 WIRE.
  
 4} A SMOKE DETECTOR IS REQUIRED BY THE
 STAIRWELL ON THE FIRST FLOOR TO COMPLY
 WITH 905.2.2 FBC.
  
 5} RECEPTACLES ARE REQUIRED TO BE ADDED
 IN THE MASTER SUITE #2 AND BEDROOM #3 TO
 COMPLY WITH 210.52(A)(2)(1). 2'OR MORE
  
 6} THE ARCHITECTS TITLE BLOCK MUST
 CONTAIN ALL THE INFORMATION REQUIRED BY
 FAC. 61G1-16.004. SEE (2), FIRM LICENSE
 NUMBER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  