Date |
Text |
2004-06-30 00:00:00 | DENIED |
| |
| 1. THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY |
| COURTHOUSEAND A COPY SUBMITTED TO THIS |
| OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 2.BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 3.SUBMIT 2 COPIES OF ALL PRODUCT |
| APPROVALS. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATIONPLEASE SEE THE STATE WEBSITE |
| AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 4.PLEASE SIGN OWNER/AGENT ON ENERGY |
| CALCS. |
| |
| 5.BASED ON SBCCI BUILDING VALUATION |
| DATA THE VALUATION HAS BEEN CHANGED TO |
| $306,800.ADDITIONAL PERMIT FEES OF |
| $1012.68 ARE DUE.SQUARE FOOTAGE HAS |
| BEEN ADJUSTED TO REFLECT PLANS. |
| 3500SQ. FT. X 76.96 = 269,360AC |
| 900SQ. FT. X 41.60 = 37,440 OTHER |
| |
| 6. SEE OTHER REVIEWERS NOTES REGARDING |
| ARCHITECT SIGNING, SEALING AND DATING |
| AND TITLE BLOCK INFO. |
| |
| 7.PLEASE SHOW ATTIC ACCESS SIZE. |
| |
| 8.PRODUCT APPROVALS ARE FOR AN |
| OUT-SWING DOOR, PLAN SHOWS INSWING. |
| PLEASE REVISE. |
| |
| 9.1015.2 HEIGHT. GUARDRAILS SHALL |
| FORM A VERTICAL PROTECTIVE BARRIER NOT |
| LESS THAN 42" HIGH. |
| 1015.3 OPENINGS. OPEN GUARDRAILS |
| SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| REJECT THE PASSAGE OF 2" DIAMETER |
| SPHERE. |
| PLEASE SHOW DETAIL ON PLAN. |
| |
| 10.A SEPERATE DEMO PERMIT IS REQUIRED |
| FOR DEMO/REMOVAL OF EXISTING BUILDING. |
| |
| ANY QUESTIONS CALL ME |
| |
| ART LANGE |
| BUILDING PLANS EXAMINER |
| 805-6672 |