Date |
Text |
2004-06-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| FBC-2001 CHAPTER 1 |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| 2) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 3) FBC-2001 424.2.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. MANUFACTURE |
| SHEETS REQUIRED. (SUBMITTAL) - SUBMITTAL |
| SHALL BE OF SUFFICIENT CLARITY TO BE |
| ABLE TO READ ALL INFORMATION. SUBMITTAL |
| SHEET HAS MANY DARK AREAS THAT MAKE THE |
| SHEET UNREADABLE IN SOME AREAS. SECTION |
| 104.2.1. |
| 4) FBC-2001 424.2.14.2 WATER RETENTION, |
| PROVIDE A POSITIVE MEANS OF RETAINING |
| WATER IN THE HEATER WHEN PUMP IS SHUT |
| OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| 5) FBC-2001 424.2.14.4 CONNECTIONS, ALL |
| WATER HEATING EQUIPMENT SHALL BE INSTAL- |
| LED WITH FLANGES OR UNION CONNECTIONS |
| ADJACENT TO THE HEATER. (ADD TO NOTES) |
| 6) SUBMIT INFORMATION FOR LENGTH OF VENT |
| PIPE ON THE ENTRAPMENT AVOIDANCE DETAIL |
| REQUIRED BY SECTION 424.2.6.6.3(2). |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |