Notes
Date Text
2004-06-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURE/FACILITIES PER TABLES 1003.1 AND
 403.1. SHOW SQUARE FOOTAGE FOR EACH
 OCCUPANCIES IN CALCULATIONS. 1 SERVICE
 SINK IS REQUIRED FOR EDUCATIONAL OCCUP-
 ANCY.
 2) SHTS A-1 & A-3 SINK SHALL COMPLY WITH
 11-4.24 AND ALL SUBSECTIONS (CONFERENCE
 ROOM). SHT A-1 SHOW CLEAR FLOOR SPACE AT
 SINK 11-4.24.5. SHT A-3 DETAIL #5, SHOW
 KNEE CLEARANCE 11-4.24.3, SINK DEPTH 11-
 4.24.4 & EXPOSED PIPES & SURFACES 11-4.
 24.6.
 3) SHT P1 DOMESTIC WATER ISOMETRIC RISER
 WATER HAMMER ARRESTOR REQUIRED AT SINK
 FOR ICE MAKER. SECTION 604.9. - WATER
 HAMMER ARRESTOR SHALL BE LOCATED NEAR
 THE FIXTURE NOT IN THE CEILING. PDI-WH
 201.
  