Plan Review Notes For Permit 04060364 |
Permit Number |
04060364 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | | | 1) SUBMIT CALCULATIONS FOR MINIMUM FIX- | | TURE/FACILITIES PER TABLES 1003.1 AND | | 403.1. SHOW SQUARE FOOTAGE FOR EACH | | OCCUPANCIES IN CALCULATIONS. 1 SERVICE | | SINK IS REQUIRED FOR EDUCATIONAL OCCUP- | | ANCY. | | 2) SHTS A-1 & A-3 SINK SHALL COMPLY WITH | | 11-4.24 AND ALL SUBSECTIONS (CONFERENCE | | ROOM). SHT A-1 SHOW CLEAR FLOOR SPACE AT | | SINK 11-4.24.5. SHT A-3 DETAIL #5, SHOW | | KNEE CLEARANCE 11-4.24.3, SINK DEPTH 11- | | 4.24.4 & EXPOSED PIPES & SURFACES 11-4. | | 24.6. | | 3) SHT P1 DOMESTIC WATER ISOMETRIC RISER | | WATER HAMMER ARRESTOR REQUIRED AT SINK | | FOR ICE MAKER. SECTION 604.9. - WATER | | HAMMER ARRESTOR SHALL BE LOCATED NEAR | | THE FIXTURE NOT IN THE CEILING. PDI-WH | | 201. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|