Plan Review Notes For Permit 04060364 |
Permit Number |
04060364 |
|
Review Stop |
MEDGAS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-22 00:00:00 | DENIED | | REFERENCE: NFPA 99C | | | | 1) MED GAS CERTIFICATIONS FOR CONTRACTOR | | AND INSTALLED ARE REQUIRED AT THE TIME | | OF APPLICATION OF MED GAS PERMIT. SECT- | | ION 4-3.1.2.15(B) | | 2) MORE INFORMATION REQUIRED FOR MED GAS | | SYSTEM. INDICATE USE FOR COMPRESSED AIR | | SYSTEM. WILL THERE BE INTAKE OF GAS BY | | HUMANS? | | 3) SUBMIT MANUF. SPECIFICATION SHEET FOR | | THE COMPRESSOR. COMPRESSORS SHALL MEET | | THE REQUIREMENTS OF SECTION 4-5.1.1.3 | | AND SECTION 2.2 MEDICAL AIR COMPRESSOR. | | 4) THE AIR INTAKE SHALL BE FROM OUTSIDE | | THE BUILDING WHEN PRACTICAL. SECTION | | 4-5.1.1.3(E). SUBMIT INFORMATION ON THE | | AIR INTAKE SYSTEM. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|