Plan Review Notes
Plan Review Notes For Permit 04060363
Permit Number 04060363
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 3.1 A DRINKING FOUNTAIN IS REQUI-
 RED PER TABLE 403.1. ALSO SEE SECTION
 410.1.
 2) SHT 3.2 ROOM 105 KITCHEN, SHOW CLEAR
 FLOOR SPACE, 11-4.24.5, TURNING AREA
 11-4.2.3, KNEE CLEARANCES 11-4.24.3,
 SINK DEPTH 11-4.24.4, & EXPOSED PIPES
 AND SURFACES 11-4.24.4. (DETAIL #3)
 3) SHT 3.2 DETAIL #6, SHOWER CONTROL
 AREA SHALL BE MIN. 38" AND MAX. 48" NOT
 48" TO CENTER OF CONTROL AS SHOWN. SECT-
 ION 11-4.21.5 & FIG 37(A), SHOWER UNIT
 11-4.21.6
 4) SHT 3.2 DETAIL #1 DOOR SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIR-
 ED FOR ANY FIXTURE. SECTION 11-4.22.2
 (SEE LAV CLEAR FLOOR SPACE)
 5) SHT 3.2 DETAIL #1 WATER CLOSET SHALL
 BE 1'6" FROM CENTER OF FIXTURE TO WALL.
 FIG. 28. SHOWS 1'7" ON DETAIL.
 6) SHT 3.2 DETAIL #5 SHOW HEIGHT AND
 CLEARANCES 11-4.19.2, EXPOSED PIPES AND
 SURFACES 11-4.19.4.
 7) SHT M1 FLOOR DRAIN IS NOT AN APPROVED
 INDIRECT WASTE INTERCEPTOR. SECTIONS
 802.3 & 802.3.2. - FLOOR SINK OR HUB
 DRAIN REQUIRED. TRAP PRIMER OR DEEP SEAL
 TRAP REQUIRED. SECTION 1002.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]