2004-06-21 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHT 3.1 A DRINKING FOUNTAIN IS REQUI- |
| RED PER TABLE 403.1. ALSO SEE SECTION |
| 410.1. |
| 2) SHT 3.2 ROOM 105 KITCHEN, SHOW CLEAR |
| FLOOR SPACE, 11-4.24.5, TURNING AREA |
| 11-4.2.3, KNEE CLEARANCES 11-4.24.3, |
| SINK DEPTH 11-4.24.4, & EXPOSED PIPES |
| AND SURFACES 11-4.24.4. (DETAIL #3) |
| 3) SHT 3.2 DETAIL #6, SHOWER CONTROL |
| AREA SHALL BE MIN. 38" AND MAX. 48" NOT |
| 48" TO CENTER OF CONTROL AS SHOWN. SECT- |
| ION 11-4.21.5 & FIG 37(A), SHOWER UNIT |
| 11-4.21.6 |
| 4) SHT 3.2 DETAIL #1 DOOR SHALL NOT |
| SWING INTO THE CLEAR FLOOR SPACE REQUIR- |
| ED FOR ANY FIXTURE. SECTION 11-4.22.2 |
| (SEE LAV CLEAR FLOOR SPACE) |
| 5) SHT 3.2 DETAIL #1 WATER CLOSET SHALL |
| BE 1'6" FROM CENTER OF FIXTURE TO WALL. |
| FIG. 28. SHOWS 1'7" ON DETAIL. |
| 6) SHT 3.2 DETAIL #5 SHOW HEIGHT AND |
| CLEARANCES 11-4.19.2, EXPOSED PIPES AND |
| SURFACES 11-4.19.4. |
| 7) SHT M1 FLOOR DRAIN IS NOT AN APPROVED |
| INDIRECT WASTE INTERCEPTOR. SECTIONS |
| 802.3 & 802.3.2. - FLOOR SINK OR HUB |
| DRAIN REQUIRED. TRAP PRIMER OR DEEP SEAL |
| TRAP REQUIRED. SECTION 1002.4. |
| |