Plan Review Notes
Plan Review Notes For Permit 04060344
Permit Number 04060344
Review Stop E
Sequence Number 3
Notes
Date Text
2004-12-27 00:00:00*** UNSAT ***
  
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW. PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE CIRCUITING FOR EM/EXT LTS IS
 PER 700.12E, THESE ARE NOT ON A SEPARATE
 CIRCUIT AS NOTED ON PLANS.
  
 2)NOTE: PLEASE SEE A PANEL SCHEDULE WAS
 SUBMITTED SIGNED AND SEALED BY THE
 ENGINEER. PLANS WHICH ARE SIGNED AND
 SEALED ARE REQUIRED TO HAVE A TITLE
 BLOCK PER FAC 61G15-23.002.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]