Plan Review Notes For Permit 04060344 |
Permit Number |
04060344 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-12-29 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | | | | | 1) FROM PREVIOUS REVIEW: | | SUBMIT A WATER RISER DIAGRAM FOR ALL | | NEW WORK. SHOW ALL PIPE SIZES AND WATER | | HAMMER ARRESTORS REQUIRED BY SECTION | | 604.9, LOCATED NEAR THE FIXTURES AS | | REQUIRED BY PDI-WH 201. | | 2) FROM PREVIOUS REVIEW: | | ATTACH WORKSHEETS, (2 SHEETS), TO EACH | | SET OF PLANS FOR REVIEW. | | ***NEW COMMENTS*** | | 3) SHT 1 OF 3 PLUMBING RISER BAY 529. NO | | SANT. DRAINAGE SHOWN FOR NEW HAND SINK. | | THE THREE COMPARTMENT SINK SHALL DRAIN | | INTO A FLOOR SINK, AS REQUIRED IN | | SECTION 802.3. PLEASE INDICATE ON | | PLANS. | | SECTION 104.2.1. | | 4) SHT 1 OF 3. PLUMBING RISER KITCHEN | | BAY 533, FOOD PREP SINK SHALL DRAIN | | INDIRECTLY PER SECTION 802.1.1. DISH | | MACHINE SHALL DRAIN INTO THE SANITARY | | SYSTEM, NOT THE GREASE WASTE SYSTEM PER | | CITY CODE. | | 5) SUBMIT RESPONSE SHEET FROM RODNEY | | COMPO, ENVIRONMENTAL COMPLIANCE FOR THE | | SIZING OF THE GREASE INTECEPTOR. WASTE | | ORD. #2938-96 | | | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|