Plan Review Notes
Plan Review Notes For Permit 04060344
Permit Number 04060344
Review Stop P
Sequence Number 2
Notes
Date Text
2004-12-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1) FROM PREVIOUS REVIEW:
 SUBMIT A WATER RISER DIAGRAM FOR ALL
 NEW WORK. SHOW ALL PIPE SIZES AND WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9, LOCATED NEAR THE FIXTURES AS
 REQUIRED BY PDI-WH 201.
 2) FROM PREVIOUS REVIEW:
 ATTACH WORKSHEETS, (2 SHEETS), TO EACH
 SET OF PLANS FOR REVIEW.
 ***NEW COMMENTS***
 3) SHT 1 OF 3 PLUMBING RISER BAY 529. NO
 SANT. DRAINAGE SHOWN FOR NEW HAND SINK.
 THE THREE COMPARTMENT SINK SHALL DRAIN
 INTO A FLOOR SINK, AS REQUIRED IN
 SECTION 802.3. PLEASE INDICATE ON
 PLANS.
 SECTION 104.2.1.
 4) SHT 1 OF 3. PLUMBING RISER KITCHEN
 BAY 533, FOOD PREP SINK SHALL DRAIN
 INDIRECTLY PER SECTION 802.1.1. DISH
 MACHINE SHALL DRAIN INTO THE SANITARY
 SYSTEM, NOT THE GREASE WASTE SYSTEM PER
 CITY CODE.
 5) SUBMIT RESPONSE SHEET FROM RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR THE
 SIZING OF THE GREASE INTECEPTOR. WASTE
 ORD. #2938-96
  
  
  
 REVIEW BY KEN STEVENS