Plan Review Notes
Plan Review Notes For Permit 04060344
Permit Number 04060344
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT A SANITARY AND WATER RISER
 DIAGRAM FOR ALL NEW WORK. SHOW ALL PIPE
 SIZES AND IF WATER HAMMER ARE USED PER
 SECTION 604.9 THEY SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING. PDI-WH 201
 2) SEPARATE GAS PLANS/PERMIT REQUIRED.
 SEE ATTACHED SHEET FOR GAS PERMIT REQ-
 UIREMENTS.
 3) ROUTE PLANS TO DBPR, HOTEL AND REST-
 URANT DIVISION FOR REVIEW. 2 SETS OF
 PLANS SHALL BE STAMPED BY DBPR AND THE
 WORKSHEETS ATTACHED TO EACH PLAN FOR RE-
 VIEW BY CITY WPB.
  